G. ELECTRICAL

All wiring must conform to the provisions of local codes or, in the absence of local codes, with the
provisions of the National Electrical Code, "Latest Edition" and this instruction manual. An equivalent type
wire must be used if any of the original wire supplied with the unit needs to be replaced.


Reference Table A for unit electrical characteristics. Bring proper service to the unit through a circuit
breaker or fused disconnect switch, in accordance with local codes. In the case of a single phase 230 VAC
unit, the neutral wire should be brought to the unit in order to provide ground service. A ground wire must
be connected to the unit at the screw or pressure connector marked "ground".

The best fuse size is the smallest fuse that will allow the equipment to operate continuously without any
nuisance trips. This type of fuse will give the equipment maximum protection. A time delay type fuse; such
as Fustat® or Fusetron®, will prevent nuisance trips due to the starting current (locked rotor amps, LRA).





All field wiring of hazardous voltages must be routed through conduit to the 7/8” access hole provided in
the base of the Control Panel.