Notice – Thermo Pride LX-13 User Manual

Page 11

Advertising
background image

11

Demand Defrost (13 Seer 1.5 ton, 14.5 Seer 1.5-4 Ton)

The control maintains proper airflow through the outdoor coil during

heating operation by melting frost and ice that may form on the coil.

Frost may accumulate unevenly in different sections of the coil because

of the arrangement of the refrigeration circuit within the coil. The control

may initiate a defrost cycle even when the coil is not completely cov-

ered with frost. This is normal operation.
The control regulates the defrost operation of the heat pump based on

accumulated compressor run time, outdoor coil temperature, and out-

door ambient temperature. The control will cause the unit to operate in

the normal heating mode until it determines that a defrost cycle is

needed.
All defrost timings are based on accumulated compressor run time.

Operation

The defrost mode is equivalent to the cooling mode except that the out-

door fan motor is de-energized. The control shall do the following to ini-

tiate a defrost cycle.

• De-energize the outdoor fan.
• Energize the reversing valve.
• Energize the auxiliary heat output through the W1/66 terminal.
• Begin the maximum defrost cycle length timer.

If the call for heating (Y) is removed from the control during the defrost

cycle, it will terminate the defrost cycle and de-energize the compres-

sor. The control will also stop the defrost cycle length timer but not reset

it. When the control receives another call for heating, it will restart the

defrost cycle and the timer at the point at which the call for heating was

removed. This will happen only if the liquid line temperature conditions

allow defrost to occur.

Defrost Curves

The control uses a set of defrost curve parameters that are selected

using the defrost curve selection jumper. The location of the defrost

curve selection jumper is shown in Figure 13. Table 4 shows the jumper

position that is appropriate for each heat pump model. Jumper position

4 is not used and the control will not allow the compressor to operate

when the jumper is in this position.

Defrost Curve Selection

The factory will place the defrost curve selection jumper in the P posi-

tion or in a numbered position appropriate for the specific heat pump

model. You should not have to change the defrost curve selection

jumper during initial installation.
If the jumper is inadvertently moved, it should be placed in the appropri-

ate numbered location based on the model number and Table 4. The

control will also not energize the compressor if the defrost curve selec-

tion jumper is in a numbered position that is not described in Table 4 or

if the defrost curve selection jumper is missing. The control will display

the proper fault code when a defrost curve jumper error is present. The

control will display the active defrost curve using the X/L terminal when

the heat pump is operating in a defrost cycle that has been forced using

the TEST inputs.

For instance, the X/L output will be energized with two flashes when

defrost curve 2 is active. The control only reads the jumper input when

the Y and W thermostat inputs are de-energized. If a jumper position is

changed while either of these inputs is energized, the control will not act

upon the jumper changes until the thermostat calls are de-energized or

power (24 VAC) to the control is cycled.

Defrost Cycle Initiation

The control will allow the heat pump to operate in the heating mode until

the combination of outdoor ambient and outdoor coil temperatures indi-

cate that a defrost cycle is necessary.
The control will initiate a defrost cycle when the liquid line temperature

is below the initiate point for the measured ambient temperature (See

Figure 13) continuously for 4-1/2 minutes. This delay eliminates unnec-

essary defrost cycles caused by refrigeration surges such as those that

occur at the start of a heating cycle.
The control will initiate a defrost cycle every 6 hours (accumulated com-

pressor run time) to recirculate refrigerant lubricants. This forced

defrost timer will be reset and restarted following the completion or ter-

mination of a defrost cycle.
The control will also initiate a defrost cycle when the TEST terminals

are shorted. This feature allows an installer or service technician to start

a defrost cycle immediately as required. When the TEST terminals are

shorted for more than six seconds with a Y input energized and the

pressure switch input is closed, the ASCD will be bypassed and the

compressor and the W1/66 terminal to auxiliary heat will be energized.
When the TEST inputs are used to force a defrost cycle, the control will

ignore the state of the liquid line temperature and outdoor ambient tem-

perature inputs. The coil does not have to be cold and the outdoor tem-

perature does not have to be within a certain range for the heat pump to

be forced into a defrost cycle. After the TEST input jumper is removed,

the defrost mode will be terminated as normal. The defrost cycle length

timer will not be started until the TEST input is removed. If the TEST ter-

minals remain shorted, the control will keep the unit in defrost mode.

Defrost Inhibition

The control will not initiate a defrost cycle if the liquid line temperature is

above 40°F unless the defrost cycle is forced using the TEST input.
The control will also prevent a defrost cycle from being initiated too

soon after the initiation of the previous defrost cycle. When power is

applied to the control and after the completion or termination of each

defrost cycle, the control will start a 40-minute timer. When this timer

expires, the control will allow another defrost cycle when needed. The

timer is based on accumulated compressor run time.

Defrost Termination

The control will terminate the defrost cycle immediately after the liquid

line temperature reaches 80°F or after eight minutes of defrost opera-

tion.
The control will do the following to terminate a defrost cycle:

• Energize the outdoor fan.

• De-energize the reversing valve.

• De-energize the auxiliary heat output through the W1/66 terminal.

• Reset and restart the 40-minute defrost inhibit timer.

Compressor Delay

When Defrost Jumper Position #2 is selected the compressor is shut

down for 30 seconds entering and exiting defrost mode. This delay is

present in normal operation but is not present when the TEST pins are

shorted to force a defrost cycle. Position #1 is recommended for recip-

rocating compressors, and Position #2 is recommended for scroll com-

pressors.

Jumper settings 1-3 are different defrost curve settings. 4 & P will not work in application.

The defrost thermostat delay will make the coil temperature about 75-
80° F. Please note that the timer will stop the circuit when R to Y is
disconnected.

NOTICE

TABLE 4:

Defrost Initiate Curves

Defrost Curve Selection

Jumper Position

1

2

3

4

All Other Models

YHJR, THJR,THRD, GHRD

YHJD, YHJF, THJD, THJF,

CHJD, CHJF, LHJD, LHJF

THGD, GHGD

None

None

Advertising
This manual is related to the following products: