8dehumidification control, Cfm selection board settings – Thermo Pride LX-13 User Manual

Page 8

Advertising
background image

8

DEHUMIDIFICATION CONTROL

A dehumidification control accessory 2HU06700124 may be used with

variable speed air handlers or furnaces in high humidity areas. This

control works with the variable speed indoor unit to provide cooling at a

reduced air flow, lowering evaporator temperature and increasing latent

capacity. The humidistat in this control opens the humidistat contacts on

humidity rise. To install, refer to instructions packaged with the acces-

sory. Prior to the installation of the dehumidification control, the jumper

across the HUMIDISTAT terminals on the indoor variable speed air han-

dler or furnace CFM selection board must be removed.
During cooling, if the relative humidity in the space is higher than the

desired set point of the dehumidification control, the variable speed

blower motor will operate at lower speed until the dehumidification con-

trol is satisfied. A 40-60% relative humidity level is recommended to

achieve optimum comfort.

If a dehumidification control is installed, it is recommended that a mini-

mum air flow of 325 cfm/ton be supplied at all times.
For connection diagrams for all UPG equipment refer to “Low Voltage

System Wiring” document available online at www.upgnet.com in the

Product Catalog Section.

CFM SELECTION BOARD SETTINGS

For proper system operation the CFM Selection control jumpers must

be set properly.
Refer to the Tabular Data Sheet for the recommended air flow settings

for each size condensing unit.
Set the cooling speed per the instructions for the air handler or furnace

by selecting the correct COOL and ADJ taps. Verify the airflow using

the LED display on the CFM selection board.

FIGURE 8:

Typical Field Wiring (Air Handler / Electrical Heat) - (Three Phase)

FIGURE 9:

Typical Field Wiring (Air Handler / Electrical Heat) (Single-Phase)

THERMOSTAT

INDOOR UNIT

OUTDOOR UNIT

LOW VOLTAGE TERMINAL BLOCK
IN AIR HANDLER WITH ELECTRIC HEAT

3,4

DEFROST
CONTROL

1

FIELD

INSTALLED
JUMPER

GND.

SCREW

CONTACTOR

T2

T1

L2

L1

M

R

Y
O

W

G

T

2

E

2

R

R

Y

Y
O

O

W2

W

C

X

G

W1

GND.

LUG

POWER WIRING
24V CONTROL WIRING
(NEC CLASS 2)

JUMPER TERMINALS E AND W TO HEAT
ON FIRST STAGE DURING EMERGENCY HEAT.

1

2

TERMINAL NOT USED ON ALL THERMOSTATS.

POWER WIRING

208/230-3-60

460-3-60

3

CHECK THE LOW VOLTAGE TERMINAL BLOCK ON THE INDOOR UNIT FOR THE ACTUAL ARRANGEMENT OF THE TERMINALS.

4

CONNECT POWER WIRING TO TERMINAL BLOCK 3TB ON UNITS WITHOUT ELECTRIC HEAT OR CIRCUIT BREAKER.

ALL FIELD WIRING TO BE IN ACCORDANCE WITH ELECTRIC CODE (NEC) AND/OR LOCAL CODES

RED

BLK

YEL

ORG

BRN

PUR

WHT

POWER

SUPPLY

208/230-3-60

460-3-60

T3

L3

W1/66

B or C

L or X

B or C

THERMOSTAT

INDOOR UNIT

OUTDOOR UNIT

LOW VOLTAGE TERMINAL BLOCK
IN AIR HANDLER WITH ELECTRIC HEAT

DEFROST
CONTROL

FIELD
INSTALLED
JUMPER

DEHUMIDIFICATION CONTROL CONNECTION
(Humidistat* Jumper must be removed)

GND.

SCREW

CONTACTOR

T2

T1

L2

L1

M

R

L or X

Y

O

W

G

T

2

E

2

R

R

Y

Y

O

O

W2

W

C

C

X/L

G

W1

BK

GND.

LUG

CIRCUIT

BREAKER***

POWER WIRING
24V CONTROL WIRING
(NEC CLASS 2)

JUMPER TERMINALS E AND W TO HEAT
ON FIRST STAGE DURING EMERGENCY HEAT.

TERMINAL NOT USED ON ALL THERMOSTATS.

POWER WIRING

208/230-1-60

230-1-50

CHECK THE LOW VOLTAGE TERMINAL BLOCK ON THE INDOOR UNIT FOR THE ACTUAL ARRANGEMENT OF THE TERMINALS.

CONNECT POWER WIRING TO TERMINAL BLOCK 3TB ON UNITS WITHOUT ELECTRIC HEAT OR CIRCUIT BREAKER.

B or C

ALL FIELD WIRING TO BE IN ACCORDANCE WITH ELECTRIC CODE (NEC) AND/OR LOCAL CODES

RED

BLK

YEL

ORG

WHT

PUR

BRN

1

2

3

4

1

3,4

W1/66

Advertising
This manual is related to the following products: