Checking for Blockage in Air-To-Air Evaporator or Condensers

1. Remove panels to gain access to coil return bends or hairpins.

2. Press SET and then press

/

to select relatively high emissivity for copper tube.

3. Start the refrigeration system.

4. Aim the thermometer at coil turn bends/hairpins.

5. Start recording temperature.

6. Take temperature of each return bend/hairpin.

• All evaporator return bends/hairpins should be at or slightly above evaporator saturation temperature from the

pressure/temperature chart.

• All condenser return bend/hairpins should be at or slightly less than condenser saturation temperature.

• If a group of return bends/hairpins do not conform to expected temperatures, that indicates a blocked

or restricted distributor or distributor tube.