ProSoft Technology MVI69-DNPSNET User Manual

Page 64

Advertising
background image

MVI69-DNPSNET ♦ CompactLogix or MicroLogix Platform

Reference

Distributed Network Protocol Interface Module

Page 64 of 119

ProSoft Technology, Inc.

November 3, 2008

5.1.2 Hardware

Specifications

Specification Description

Dimensions

Standard 1769 Single-slot module

Current Load

800 mA max@ 5 VDC
Power supply distance rating of 2 (L43 and L45
installations on first 2 slots of 1769 bus)

Operating Temp.

0 to 60°C (32 to 140°F)

Storage Temp.

-40 to 85°C (-40 to 185°F)

Relative Humidity

5 to 95% (non-condensing)

LED Indicators

Power and Module Status
Application Status
CFG Port Activity
Ethernet Port Activity
Error Status

CFG Port (CFG)

RJ45 (DB-9M with supplied cable)
RS-232 only
No hardware handshaking

App Port (Ethernet modules)

10/100 Base-T Ethernet compatible interface
Electrical Isolation 1500 V rms at 50 Hz to 60 Hz for 60 s,
applied as specified in section 5.3.2 of IEC 60950: 1991

Ethernet Broadcast Storm Resiliency = less than or equal
to 5000 [ARP] frames-per-second and less than or equal
to 5 minutes duration

Shipped with Unit

RJ45 to DB-9M cables for each port
6-foot RS-232 configuration Cable

5.1.3 Functional

Specifications

The MVI69-DNPSNET module accepts DNP commands to control and monitor
the data stored in the DNP databases. This data is passed between the module
and the CompactLogix processor over the backplane for use in user applications.

ƒ DNP databases to house data for the slave port supporting the following

maximum point counts

o

Binary input: 8000 points (500 words)

o

Binary output: 8000 points (500 words)

o

Counter: 250 (500 words)

o

Analog input: 500 words

o

Analog output: 500 words

o

Float input: 150 points (300 words)

o

Float output: 150 points (300 words)

ƒ User-definable module memory usage up to maximum point counts
ƒ Data movement between module using Input/Output image
ƒ Ethernet port supporting both TCP and UDP over Ethernet
ƒ Supports DNP 3.0 in a level 2 implementation
ƒ Supports sending of input event data from the ladder to the module
ƒ Supports time synchronization from/to processor
ƒ Configurable via text file
ƒ Status and error information
ƒ All data in the DNP slave is contained in user-defined files

Advertising