ProSoft Technology MVI69-DNPSNET User Manual

Page 76

Advertising
background image

MVI69-DNPSNET ♦ CompactLogix or MicroLogix Platform

Reference

Distributed Network Protocol Interface Module

Page 76 of 119

ProSoft Technology, Inc.

November 3, 2008

Word Offset in Block

Data Field(s)

Description

3 Sequence

Counter

This field contains the sequence counter of the
last successful block 9959 received.

4 to n

Spare

Not used

Block 9970 - Set Processor Time Using Module Time

This block transfers the module's time to the processor. Ladder logic must be
used to set the processor's clock using the data received. The format of the block
sent from the processor has the following format:

Block Format for Write

Word Offset in Block

Data Field(s)

Description

0 Block

ID

This field contains the value of 9970 identifying
the block type to the module.

1 to n

Not Used

Not Used

The module will respond to a valid block 9970 request with a block containing the
requested date and time. The following example shows the format of this block.

Block Format for Read

Word Offset in Block

Data Field(s)

Description

0

Block Read ID

This field contains the block identification code of
9970 for the block.

1

Block Write ID

This is the next block requested by the module.

2 Year

This field contains the four-digit year to be used
with the new time value.

3 Month

This field contains the month value for the new
time. Valid entry for this field is in the range of 1
to 12.

4 Day

This field contains the day value for the new
time. Valid entry for this field is in the range of 1
to 31.

5 Hour

This field contains the hour value for the new
time. Valid entry for this field is in the range of 0
to 23.

6 Minute

This field contains the minute value for the new
time. Valid entry for this field is in the range of 0
to 59.

7 Seconds

This field contains the second value for the new
time. Valid entry for this field is in the range of 0
to 59.

8 Milliseconds

This field contains the millisecond value for the
new time. Valid entry for this field is in the range
of 0 to 999.

9

Remote Time
Synchronization

This field informs the PLC if the date and time
passed has been synchronized with a remote
DNP master device on the module's slave port.

10 to n

Not Used

Not Used

Advertising
This manual is related to the following products: