MVI56-AFC ♦ ControlLogix Platform

MVI56-AFC Sample Logic

Liquid and Gas Flow Computer

User Manual

ProSoft Technology, Inc.

Page 229 of 316

February 25, 2011

The following is an example for Meter 1:

12.3.8 Meter Signals

Command

Use this Controller Tag

Description

Enable

AFC56.MeterSignals.Enable

This value should be set as 1 in order to
enable the command. If this value is 0 the

module will ignore the reset commands

from the ladder

Select Meter

AFC56.MeterSignals.Meter

Select the meter number (1 to 16) for the

reset command

Select Action

AFC56.MeterSignals.Action

Select the action to execute (Select

Stream or Reset Resettable Accumulator)

Select Signals

AFC56.MeterSignals.Signals

AFC56.MeterSignals.ResetOnce

AFC56.MeterSignals.LastBlockID

Note: The AFC56.MeterSignals.BID and AFC56.MeterSignals.Action tags are automatically
updated by the ladder logic so you do not have to enter any value for this tag.


The following illustration shows the meter signals data structure.