ProSoft Technology MVI56-AFC User Manual

Page 267

Advertising
background image

MVI56-AFC ♦ ControlLogix Platform

Diagnostics and Troubleshooting

Liquid and Gas Flow Computer

User Manual

ProSoft Technology, Inc.

Page 267 of 316

February 25, 2011

O2 oxygen 0
iC4 iso-butane 0
nC4 normal butane 0
iC5 iso-pentane 0
nC5 normal pentane 0
C6 hexane 0
C7 heptane 0
C8 octane 0
C9 nonane 0
C10 decane 0
He helium 0
Ar argon 0
neoC5 neopentane 0
Ux user1 0
Uy user2 0



AFC-56(16) Audit Date: 16-09-2002 16:18:08
Site Name: MVI Flow Station
Project: AFC
_______________________________________________________________________
Meter 1:
Tag M01
Wallclock 0000/00/00.00:00:00
Barometric pressurekPaa 101,325
Viscosity 0,010268
Orifice/pipe geometric parameters
Orifice plate Meter tube
Temperature 68 68
Diameter 1 2
Coefficient 9,25E-06 0,0000062
_______________________________________________________________________
Scan 2
Temperature (Floating point) 15
Pressure (Floating point) 1000
Dif. pressure (Floating point) 22
Temperature (°F) 15
Pressure (psig) 1000
Dif. pressure (hw) 22
Scan period (second) 0,495
Specific gravity 0,7404104
Fpv 0
Compressibility flowing 0,9051347
Compressibility reference 0,9989105
Diameter at T tube 1,999343
Diameter at T orifice 0,9995098
Velocity of approach factor ev 1,032773
Pressure extension xt 149,4683
Coefficient of discharge cd 0,6042569
Expansion factor y 0,9997441
Composition factor 0,2728558
Mass flow Qh 2280,571
Orifice characterization error 0
Analysis characterization error 0
AGA8 calculation error 0

Advertising