Meter Channel Functionality

MVI56-AFC ♦ ControlLogix Platform

User Manual

Liquid and Gas Flow Computer

Page 34 of 316

ProSoft Technology, Inc.

February 25, 2011

3.3

Differential (Orifice) Meter Overview

The static pressure of the gas stream can be measured either upstream of the

meter (before the differential pressure drop), or downstream of the meter (after

the pressure drop). Both AGA3 and AGA8 require the upstream static pressure

for their calculations, where:
upstream pressure = downstream pressure + differential pressure
If the pressure is measured from a downstream tap (typical), the Downstream
Static Pressure
option should be set through the AFC Manager.
The module also supports the V-Cone device. You can configure V-Cone meters

and downstream selections in AFC Manager, on the Meter Configuration /
Calculation Options
dialog box.

3.3.1 Primary Input = Differential Pressure

The primary input parameter configures the value used as source for the

accumulator calculation. If the parameter is set to Differential Pressure, the

module uses the differential pressure value transferred through the backplane for

accumulator calculation.

3.3.2 Primary Input = Flow Rate

You can configure the primary input parameter as flow rate in order to use this

value for the accumulator calculation.

Note: The flow rate can be converted to a different unit.

The AFC Manager software supports the following parameters:
 Orifice Plate and Meter Tube Measured Diameter
 Orifice Plate and Meter Tube Measurement Temperature
 Orifice Plate and Meter Tube, Coefficient of Thermal Expansion
 DP Flow Threshold (kPa)
 DP Alarm Threshold (kPa)