MVI56-PDPMV1 ♦ ControlLogix Platform

Mailbox Messaging

PROFIBUS DPV1 Master

User Manual

ProSoft Technology, Inc.

Page 161 of 255

March 22, 2011

Message Information
Refer to Message Information (page 173).

Station Type [0 … 126]
00h: Slave Station
01h: Master Station not yet ready for Token ring (station only physically at the

bus)
02h: Master Station ready to enter Token ring (there is not yet any Token

transmission)
03h: Master Station in Token Ring (Token transmission through the station)
04h: Station does not exist

Fault Information
If "Invalid Other" is returned in the Message Information word in the header of the

response, information about the fault can be found here. Refer to Message

Information (page 173).
0AH00: Failed to build Live List.
FF00h: Module offline (not initialized or no valid database)

3.5.6 Mailbox Message: Acyclic Data Read: Class 1

This command initiates a DPV1 Class 1 acyclic read request. Refer to EN50170

(DPV1) for more information.

Parameter

Description

Command Initiator

Application

Command Name

MSAC1 READ

Command Number

2000h

Fragmented

No

Extended Header Data

Fault information may be returned in the header of the response.