Byte Offset

Start

End

Name

Description

74

74

PROFIBUS pad byte to make data word aligned (not used)

75

75

PROFIBUS Master Operating
State

PROFIBUS Master operating state
0x0000=Offline
0x4000=Stop
0x8000=Clear
0xC000=Operate

76

77

PROFIBUS Ident Number

PROFIBUS Master PNO Ident number. Bytes will be swapped

78

81

PROFIBUS Master Serial Number Unique 32-bit serial number for the PROFIBUS Master

82

83

PROFIBUS Software Version

Software version number for the PROFIBUS Master software
Example for Version 1.40:
High Byte - 0x40
Low Byte - 0x01

84

85

PROFIBUS Master Module Status Represents the PROFIBUS Master module’s operating status

Bit 2=Application Status
0 - Application Stopped
1 - Application Running
Bit 8=Data exchange (FBRS)
0 - There is no data exchange with any of the assigned slaves
1 - There is data exchange with at least one of the assigned
slaves
Bit 9=Slave input frozen/cleared (FBFC)
0 - A slave's inputs in the IN area are cleared if a slave is not in
Data Exchange
1 - A slave’s inputs in the IN area are frozen if a slave is not in
Data Exchange
Bit 12=Reset (RDR)
0 - No action
1 - A reset is requested by the PROFIBUS Master module
because a new database has been downloaded

86

89

PROFIBUS configuration
Checksum

CRC32 checksum for PROFIBUS Master configuration
downloaded from configuration utility

90

93

MVI56 Module configuration
checksum

MVI56-PDPMV1 for module configuration downloaded from
configuration utility

94

95

Application program scan counter

MVI56-PDPMV1 module program scan counter. Can be used to
gauge application code scan time performance

96

97

Module PROFIBUS output image
data update counter

Counter representing the number of times the output data image
is transferred to the module’s internal Master

98

99

Module PROFIBUS input image
data update counter

Counter representing the number of times the input data image
is transferred from the module’s internal Master

100

101

Module out mailbox counter

Module out mailbox counter

102

103

Module in mailbox counter

Module in mailbox counter

104

105

Module alarm IND receive counter Number of spontaneous alarm messages received from slave

106

107

Module alarm CON receive
counter

Number of confirmation messages received from slaves
indicating that the slave received the confirmation message from
the MVI56-PDPMV1 module

108

109

Reserved

Reserved for future use