IMPORTANT: ControlLogix Version 16 with FLEX Mode
If you change the connection sizes in the module profile, you must also update the following data
types with the new sizes. The connection I/O sizes defined in the module profile must always
match the following user-defined data types:
PDPMV1_C

ONNECTION

_I

NPUT

PDPMV1_C

ONNECTION

_O

UTPUT

You will also need to adjust limits in some of the ladder logic or AOI logic. For additional details,
see Adjusting the Connection Sizes for Your Application. (page 41)

The array sizes must be modified (in the Data Type column) to match the

connection sizes configured in the module profile. Failure to do so will prevent

the module from establishing backplane communication with the ControlLogix

processor.

Example 1
For the following example, if the module profile is configured as: