MVI56-PDPMV1 ♦ ControlLogix Platform

Diagnostics and Troubleshooting

PROFIBUS DPV1 Master

User Manual

ProSoft Technology, Inc.

Page 181 of 255

March 22, 2011

Processor
Status

Module
Status

PROFIBUS Master
Status

PROFIBUS Master
Status LED Description

PROFIBUS
Master is

stopped

RUN

ACTIVE

COM STAT (OFF):
Master is not

communicating with

configured slaves.
DBASE STAT (GREEN):
PROFIBUS has been

configured.
TKN HOLD (GREEN):
Module is holding the

PROFIBUS token.
MSTR STAT (RED):
Master is in STOP mode.

CPU is in
Program

mode

PROG

ACTIVE

COM STAT (OFF):
Master is not

communicating with

configured slaves.
DBASE STAT (GREEN):
PROFIBUS has been

configured.
TKN HOLD (GREEN):
Module is holding the

PROFIBUS token.
MSTR STAT (RED):
Master is in STOP mode.

CPU is in
Program

mode

PROG

ACTIVE

COM STAT (OFF):
Master is operating but

there are no slaves

responding.
DBASE STAT (GREEN):
PROFIBUS has been

configured.
TKN HOLD (GREEN):
Module is holding the

PROFIBUS token.
MSTR STAT (GREEN):
Master is in operating

mode.


As previously indicated in this User Manual, the module requires the correct

sample program loaded to the processor for correct initialization and operation. If

the sample program is not set up correctly, then the module might not fully

initialize or allow access to the debug menu through PCB.
As indicated below, it is required to have a sample program loaded in the

processor in order to allow debug menu access through PCB and to be able to

reconfigure the MVI56-PDPMV1 module.
Also, if you observe the MSTR STAT LED as RED or blinking GREEN/RED it

means that an incorrect sample ladder logic was loaded to the processor (not

matching the actual module mode (LEGACY or FLEX).