Venting fireplace - top, Venting graph (dimensions in feet) – Empire Comfort Systems DVP48FP3 EN User Manual

Page 15

Advertising
background image

21759-6-0608

Page 15

To Use the Vent Graph (Figure 19)

1. Determine the height of the center of the horizontal vent

pipe. Using this dimension on the Sidewall Vent Graph,

locate the point it intersects with the slanted graph

line.

2. From the point of this intersection, draw a vertical line

to the bottom of the graph.

3. Select the indicated dimension, and position the unit in

accordance with same.

EXAMPLE A:

If the vertical dimension from the floor of the unit is 35

feet, the horizontal run to the outer wall flange must not

exceed 6.5 feet.
EXAMPLE B:

If the vertical dimension from the floor of the unit is 6.5

feet, the horizontal run to the outer wall flange must not

exceed 14.5 feet.
Special Note: For each 45 degree elbow installed in the

horizontal run, the length of the horizontal run MUST be

reduced by 18" (45cm). This does not apply if the 45 degree

elbows are installed on the vertical part of the vent system.

Reduce 3' for every 90° elbow.
Example: According to the chart the maximum horizontal

vent length is 20' and if two 45 degree elbows are required

in the horizontal vent it must be reduced to 17'.
The maximum number of 45 degree elbows permitted per

side wall installation is two (2). These elbows can be installed

in either the vertical or horizontal run.
Note: On vertical venting the first elbow does not get

counted.

Figure 19

Acceptable vertical and horizontal vent run.

(40' maximum vertical and 20' maximum horizontal)

Unacceptable vertical and horizontal vent run.

VERTICAL

DIMENSION

FROM

THE

BOTTOM

OF

THE

UNIT

TO

THE

CENTER

OF

THE

FLUE

OUTLET

WITH

VERTICAL

OR

HORIZONTAL

TERMINATION

CAPS

Venting Graph (Dimensions in Feet)

VENTING FIREPLACE - TOP

Advertising
This manual is related to the following products: