Empire Comfort Systems DVP48FP3 EN User Manual

Page 55

Advertising
background image

21759-6-0608

Page 55

Important

1. The following service procedures are provided as a general

guide.

2. Meter readings between gas control and ignition module must

be taken within the trial for ignition period. Once the igni-

tion module locks out, the system must be reset by setting the

thermostat down for at least one minute before continuing.

3. If any component does not function properly, make sure it is

correctly installed and wired before replacing it.

4. The ignition module cannot be repaired. If it malfunctions, it

must be replaced.

5. Only trained, experienced service technicians should service

intermittent pilot systems.

Perform the

CHECKOUT steps on page 53 as the first step in

troubleshooting. Then check TROUBLESHOOTING GUIDE

to pinpoint the cause of the problem. If troubleshooting indicates

an ignition problem, see Ignition System Checks below to isolate

and correct the problem.
Following troubleshooting, perform the

CHECKOUT procedure

(page 53) again to be sure system is operating normally.
Ignition System Checks

Step 1: Check ignition cable.

Make sure:

A. Ignition cable does not touch any metal surfaces.

B. Ignition cable is no more than 36 inches long.

C. Connections to the ignition module and to the igniter-sensor

are clean and tight.

D. Ignition cable provides good electrical continuity.
Step 2: Check ignition system grounding.

Nuisance shutdowns are often caused by a poor or erratic

ground.

A. A common ground, usually supplied by the pilot burner bracket,

is required for the module and the pilot burner/igniter sen-

sor.

• Check for good metal-to-metal contact between the pilot

burner bracket and the main burner.

• Check the ground lead from GND (BURNER) terminal on

the module to the pilot burner. Make sure connections are

clean and tight. If the wire is damaged or deteriorated, replace

it with No. 14-18 gauge, moisture-resistant, thermoplastic

insulated wire with 105 C (221 F) minimum rating.

• If flame rod or bracket are bent out of position, restore to

correct position.

• Replace pilot burner/igniter sensor if insulator is

cracked.

Step 3: Check spark ignition circuit. You will need a short jumper

wire made from ignition cable or other heavily insulated

wire.

A. Close the manual gas valve.

B. Disconnect the ignition cable at the SPARK terminal on the

module.

WARNING

When performing the following steps, do not touch stripped

end of jumper or SPARK terminal. The ignition circuit

generates 13,000 volts at 25 pf load and electrical shock

can result.

C. Energize the module and immediately touch one end of the

jumper firmly to the GND terminal on the module. Move the

free end of the jumper slowly toward the SPARK terminal until

a spark is established.

D. Pull the jumper slowly away from the terminal and note the

length of the gap when sparking stops. Check table below.

Step 4: Check pilot flame current.

A. Turn off furnace at thermostat.

B. Disconnect main valve wire from the TH or MV terminal on

the gas control.

C. Disconnect ground wire from GND (BURNER) terminal at

module.

D. Connect a meter (dc microamp scale) in series with the ground

lead.

• Disconnect ground lead from GND terminal on ignition

module.

• Connect the black (negative) meter lead to the ignition

module GND (BURNER) terminal.

• Connect the red (positive) meter lead to the free end of the

ground lead.

E. Set thermostat to call for heat. The spark will light the pilot but

the main burner will not light because the main valve actuator

is disconnected.

F. Read the meter. The flame sensor current must be steady and

at least 1.0 uA.

G. If the reading is less than the minimum or unsteady,

• Make sure pilot flame envelopes 3/8 to 1/2 inch of the flame

rod.

• If necessary, adjust pilot flame by turning the pilot adjustment

screw on the gas control clockwise to decrease or counter-

clockwise to increase pilot flame. Following adjustment,

always replace pilot adjustment cover screw and tighten

firmly to assure proper gas control operation.

• Check for cracked ceramic insulator, which can cause short

to ground, and replace igniter-sensor if necessary.

• Make sure electrical connections are clean and tight. Replace

damaged wire with moisture-resistant No. 18 wire rated for

continuous duty up to 105 C (221 F).

H. Remove meter and reconnect all wires. Return system to

normal operation before leaving job.

ARC LENGTH

ACTION

No arc or arc less than 1/8

inch.

Arc 1/8 inch or longer

Check external fuse, if provided.

Verify power and module input

terminal.

Replace module if fuse and power

okay.

Voltage output is okay.

Advertising
This manual is related to the following products: