INSTALLATION MANUAL

©

SYMPTOM

CAUSE

SOLUTION

No source or zone selected
from RS-232 controller.

1. RS-232 controller incorrectly
programmed.

Verify/correct programming.

Verify RS-232 wiring. Check wire
integrity an pin-out configuration.

RS-232 Control

2. RS-232 signal path wiring bad.

Incorrect source and/or zone
selected.

The V883 RS-232 commands
were incorrectly programmed.

Verify/correct programming.

3. UNIT ID DIP switches incorrect. Verify/correct DIP switches.

4. BAUD RATE switches incorrect. Verify/correct DIP switches.

Acknowledgement
&V883,ACK,xxx<CR> is not
received within 200ms

1. The command was formatted
incorrectly.

Verify/correct programming.

2. An error has occurred in the
V883.

Turn unit OFF, then back ON.

3. Serial cable not connected
or defective.

Connect or replace serial cable.

4. V883 does not have power.

Connect power, check breakers.

SYMPTOM

CAUSE

SOLUTION

No source or zone selected
from VIA!NET controller (VIA!
Touch Panel, etc.).

1. VIA!NET controller not
programmed.

Program VIA!NET controller.

Verify VIA!NET wiring.

VIA!NET Control

2. VIA!NET signal path wiring bad.

Incorrect source and/or zone
selected.

Incorrect V883 VIA!NET com-
mands programmed.

Verify/correct programming.

3. UNIT ID DIP switches incorrect. Verify/correct DIP switches.