Energy Tech Laboratories MR212 User Manual

Page 13

Advertising
background image

13

Adjust pilot flame.

Lock unit into

high fire.

Adjust

incoming gas

pressure.

Does high fire produce

at least a 70°F temp

rise and produce the

correct manifold

pressure?

Adjust high fire

No

Lock unit into low fire.

Yes

Does thin flame fill

entire burner length?

Adjust low

fire.

Setting incoming pressure:
Presure must be measured at first "T" in
supply gas line before the first gas valve.

Adjusting the pilot:
The pilot DC signal should be 12 VDC
minimum.

Adjusting high fire:
High fire manifold pressure should be 5"
maximum for natural gas and 2.5"
maximum for propane. High fire should
produce at least a 70°F temperature rise.
Remove wire #4 from the Maxitrol 14
amplifier (#2 and #4 for Maxitrol 44).
This will drive the valve into its full open
position. Adjust high fire with the
regulator inside the unit. Turn clockwise
to increase temperature rise. Ensure that
DC flame signal is minimum 12 VDC.
Replace the wires on the Maxitrol
Amplifier.

Adjusting low fire:
Remove wire #5 from the Maxitrol 14
amplifier (#8 for Maxitrol 44). This will
drive the valve into its lowest position.
Adjust the low fire by turning the low fire
bypass screw on the side of teh
modulating valve for M511 and M611
models. For MR212 valves, the low and
high fire are both under the valve cover.
Refer to the included Maxitrol literature
for more detailed information. Ensure
that DC flame signal is minimum 12 VDC
and that the enite length of burner is filled
with a thin flame.

Yes

No

No

Burner start up

complete.

Yes

Is incoming gas pressure

7"-14"?

(7"-5 psi. for size 4-5 units)

Heater Start Up Summary


Advertising