23

Remote Panel Troubleshooting Chart

Light Indication

Condition

Possible Cause

No Lights

Power not available to Remote Panel

Bad voltage to unit
Main disconnect in “OFF” Position
Circuit breaker tripped
Bad main transformer

POWER Light Only

Proper unit Off Operation

No problem

No power to motor starter

Manual/Off/Auto Switch in “Off” Position
(3 Position Remote Panels Only)
Improper damper function
Low Temperature Thermostat Timed
Out (Option)

POWER Light and
BLOWER ON Light

Proper Ventilation Operation

No Problem

No Power to Flame Safety Controller

Manual/Off/Auto Switch in “Off” Position
(2 Position Remote Panels Only)
Heat/Vent Switch in “Vent” Position
Gas Pressure Switch Tripped (option)
High Temperature Limit Thermostat
Tripped
Manual/Off/Auto Switch in “Auto”
Position and Intake Air Thermostat not
Satisfied

Improper Airflow

Insufficient Airflow
Excessive Airflow
Bad airflow switch
Problem with air probes
Problem with airflow tubing
Broken Belt

POWER Light and
BLOWER ON Light and
BURNER ON Light

Proper Heating Operation

No Problem

CLOGGED FILTER Light On
(Optional)

Filters Clogged

Filters Dirty or Need Replacement

FLAME FAILURE Light On

Flame Safety Alarm Activated

No Flame Detected during Pilot
Establishment Period

Combination Valve in “Off” Position
(Unit Sizes 1-3)
Stuck Closed Gas Valve
No or Low Gas Pressure
Bad Spark Electrode
Bad Ignition Transformer
Flames Sensor Malfunction
Clogged Pilot Orifices