Remote panel option – Energy Tech Laboratories MR212 User Manual

Page 20

Advertising
background image

20

Remote Panel Option

The Remote Panel is a device used to control the operation of the heater from a remote location. This
unit is available in both a “2 Position” or “3 Position” configuration and with or without a cooling output. It
also will accommodate both the Maxitrol discharge temperature dial and the Maxitrol space sensing
Selectrastat. It is important to understand the following Remote Panel controls and uses:

1. Manual/Off/Auto

Switch

- Used to control blower operation and tempering mode of unit. The

AUTO position allows the unit to “decide”, through the use of the intake air thermostat, whether or
not heating is needed. The MANUAL position allows the user to control whether or not heat is
needed. The OFF position will turn the blower off when a “3 Position” remote panel is ordered.
The OFF position will disable all temperature controls when a “2 Position” remote panel is
ordered and fan power is then controlled by the pre-wire package only.


2. Heat/Vent Switch –
This switch is powered when the Manual/Off/Auto switch is in the MANUAL

position. It is used to control the tempering mode of the unit. The VENT position will prevent the
burner from operating and the heater will deliver untempered air. The HEAT position will force
the burner on and the unit will heat the incoming air. This switch becomes a Heat/Vent/Cool
switch when the cooling interlock is ordered. This option provides a 120V cooling output from the
remote panel.


3. Lights-

Displays the current status of unit features. The light definitions are as follows:

POWER - Illuminated when there is power to Remote Panel.
BLOWER ON - Illuminated when the blower motor is powered.
BURNER ON - Illuminates after pilot flame has established and main valve is powered.
FLAME FAILURE - Illuminated when the Flame Safety Control is in Alarm mode.
CLOGGED FILTER – (Optional) Illuminated when the Intake Filters are Dirty.


4. Temperature Control –
Controls the discharge temperature of a standard unit. The temperature

dial is replaced with Maxitrol Selectrastat in Space Heating applications and is used to control the
space temperature.

1

2

3

4

CLOGGED
FILTER

FLAME
FAILURE

Advertising