Eaton 9155 at-a-glance, Front view of 3-high module with cover off – Eaton 9155 User Manual

Page 6

Advertising
background image

Eaton 9155 at-a-glance

Model Selection Table - Eaton 9155 UPS (8–15 kVA)

Order Number

1

Description

Power Rating

2

(kVA/kW)

Input & Output

Connection

4

Output Receptacles

Dimensions

H x W x D

5

(in)

Unit

Weight

3

(lb)

K4081100000

PW9155 Model 8 - 32 Battery (2-high)

8/7.2

Hardwired

See PDM chart

32.2 x 12.0 x 32.0

352

K4081200000

PW9155 Model 8 - 64 Battery (3-high)

8/7.2

Hardwired

See PDM chart

47.8 x 12.0 x 32.0

590

K4081300000

PW9155 Model 8 - 32 Battery with Transformer (3-high)

8/7.2

Hardwired

See PDM chart

47.8 x 12.0 x 32.0

558

K4101100000

PW9155 Model 10 - 32 Battery (2- high)

10/9

Hardwired

See PDM chart

32.2 x 12.0 x 32.0

352

K4101200000

PW9155 Model 10 - 64 Battery (3- high)

10/9

Hardwired

See PDM chart

47.8 x 12.0 x 32.0

590

K4101300000

PW9155 Model 10 - 32 Battery with Transformer (3-high)

10/9

Hardwired

See PDM chart

47.8 x 12.0 x 32.0

558

K4121100000

PW9155 Model 12 - 32 Battery (2-high)

12/10.8

Hardwired

See PDM chart

32.2 x 12.0 x 32.0

352

K4121200000

PW9155 Model 12 - 64 Battery (3-high)

12/10.8

Hardwired

See PDM chart

47.8 x 12.0 x 32.0

590

K4121300000

PW9155 Model 12 - 32 Battery with Transformer (3-high)

12/10.8

Hardwired

See PDM chart

47.8 x 12.0 x 32.0

558

K4151100000

PW9155 Model 15 - 32 Battery (2- high)

15/13.5

Hardwired

See PDM chart

32.2 x 12.0 x 32.0

352

K4151200000

PW9155 Model 15 - 64 Battery (3- high)

15/13.5

Hardwired

See PDM chart

47.8 x 12.0 x 32.0

590

K4151300000

PW9155 Model 15 - 32 Battery with Transformer. (3- high) 15/13.5

Hardwired

See PDM chart

47.8 x 12.0 x 32.0

558

1. 50/60 Hz auto-sensing. All models can be used for frequency/phase conversion with de-rated 80% load. Please refer to manual for details.

2. Input voltage 200–240V with neutral or with optional input isolation transformer. Output voltages are user-selectable 100/200, 110/220,

120/240 Vac 180° phase displacement, or 120/208, 127/220 Vac 120° phase displacement.

3. Weight is installed weight; add 47 lbs (2-high models) or 50 lbs (3-high models) to determine shipping weight.

4. An input neutral is required for all configurations unless the input isolation transformer is used.

5. Depth increases to 33.7" when unit is configured with a PDM.

Four button graphical

LCD with backlight

X-Slot Communication Bay #1

Fans

Signal Input 1
Signal Input 2

REPO (normally open)

REPO (normally closed)

X-Slot Communication Bay #2

DB-9 Communication Port

Relay Contact

Internal batteries on slide

out trays (field-replaceable)

Front view of 3-high module

with cover off

6

EATON CORPORATION 9155 UPS

Advertising