Ventilation and Combustion Air

Wall furnaces shall be installed in a location in which the facilities for

ventilation permit satisfactory combustion of gas and proper venting

under normal conditions. In buildings of conventional frame, brick, or

stone construction without tight storm windows and doors, infiltration

is normally adequate to provide air for combustion and draft hood dilu-

tion.

Where appliances are installed in confined and unconfined spaces

within a building, the building being of unusually tight construction, air

for combustion and ventilation must be obtained directly from outdoors

or from such spaces that freely communicate with the outdoors. Under

these conditions, the confined and unconfined spaces shall be provided

with two permanent openings, one near the top of the enclosure and one

near the bottom; each opening shall have a free area of not less than one

square inch (6.45cm

2

) per 2,000 BTU hr. (.6KW/H) of total input.

Qualified Installing Agency

Installation and replacement of gas piping, gas utilization equipment or

accessories and repair and servicing of equipment shall be performed

only by a qualified agency. The term “qualified agency” means any indi-

vidual, firm, corporation or company which either in person or through

a representative is engaged in and is responsible for (a) the installation

or replacement of gas piping or (b) the connection, installation, repair or

servicing of equipment, who is experienced in such work, familiar with

all precautions required and has complied with all the requirements of

the authority having jurisdiction.

The installation must conform with local codes or, in the absence of

local codes, with the National Fuel Gas Code, ANSI Z223.1/NFPA 54*

Natural Gas and Propane Installation Code, CSA B149.1.

*Available from the American National Standards Institute, Inc., 11

West 42nd St., New York, N.Y. 10036.
Clearances

1. In selecting a location for installation , it is necessary to provide

adequate accessibility clearances for servicing and proper installa-

tion.

2. The FAW-55 can be attached to the wall or recessed into the wall up

to 4 inches (102mm) in depth.

3. The wall in which the furnace is recessed has (0) zero (0mm) clear-

ance to the furnace sides and top.

4. When using side discharge registers, SOR-1 or SOK-1, the furnace

cannot be recessed into the wall.

5. Clearance to sidewall or combustible material is 4 inches

(102mm).

6. Ceiling clearance is 7 1/2 inches (191mm)

7. Floor and rear wall clearance is (0) zero inches (0mm).

8. Clearance of 18 inches (457mm) is required to adjacent wall or com-

bustible material when flushed mounted SOR-1, side outlet register

is used.

Before Installing Consider The Following Venting

1. A chimney for residential-type or low-heat gas utilization equipment

shall extend at least 3 feet (914mm) above the highest point where it

passes through a roof of a building and at least 2 feet (610mm) higher

than any portion of building within a horizontal distance of 10 feet

(3m).

2. This furnace must not be connected to a chimney flue serving a

separate solid-fuel burning appliance.

3. Uninsulated Single-Wall Metal Pipe shall not be used outdoors in

cold climates for venting gas utilization equipment.

4. Attention! This Fan Type Vented Wall Furnace is equipped with a

vent safety switch. In the event of spillage of flue products due to

improper venting the vent safety switch will open, which results in

State of Massachusetts: The installation must be made by a

licensed plumber or gas fitter in the Commonwealth of Mas-

sachusetts.

the main burners to “shut off.”

Refer to Figure 1 and Page 12 for additional information regarding U.L.

Listed gas vent equipment.
Installing Optional Side Outlets

Side outlet register, SOR-1 may be installed on one or both sides of the

furnace at the required clearances of 18 inches (457mm) to adjacent wall

or combustible material as shown in Figure 2.
1. Locate and cut the 5 1/2” (140mm) square opening in the cabinet side

using the template from the kit, exposing the inner liner knock-out.

2. Remove the knock-out.

3. Place the register on the 5 1/2” (140mm) opening with the louvers

set for the desired direction and mark the mounting holes using the

register as a template.

4. Drill two (2) 1/8” (3mm) diameter holes in cabinet side and fasten the

register in place with two (2) #10 x 1” (25mm) screws provided.

Side outlet kit, 10” (254mm) boot assembly with register, SOK-1 for warm

air discharge into an adjoining room may be installed on either side of the

furnace at the required clearance of 4 inches (102mm) to adjacent wall as

shown in Figure 3A.
1. Locate and cut the 5 1/2” (140mm) square opening in the cabinet side

using the template from the kit, exposing the inner liner knock-out.

2. Remove the knock-out.

3. Using the inner and outer boots as hole templates, mark and drill (8)

1/8” (3mm) diameter holes in the inner liner and cabinet side.

4. Using Figure 3A locate and cut a 6 3/4” (171mm) square opening

through walls.

5. Attach furnace to wall (see Attaching Furnace to Wall).

6. With furnace in place, after checking alignment of side outlet opening

in wall and furnace, place the 9 3/8” x 9 3/8” (238mm x 238mm) side

outlet wall plate over outer boot, pass the outer boot through the wall

and attach side outlet wall plate to furnace side of wall with (2) #10

x 1” (25mm) screws provided.

7. Fasten outer boot to the cabinet side with (4) #8 x 1/4” (6mm) screws

provided.

8. Position and attach inner boot to inner liner with (4) #8 x 1/4” (6mm)

screws provided.

9. Locate the register with its louvers positioned for the desired air

discharge direction and mark the mounting holes using the register

as a template.

10.Drill (2) 1/8” (3mm) diameter holes in the wall and fasten the register

in place with (2) #10 x 1” (25mm) screws provided.

Installing Optional Rear Outlet

Rear outlet kit, 10” (254mm) boot assembly with register, ROK-1 for warm

air discharge into an adjoining room.
Attention: Before furnace is attached to the wall, the wall opening for

the rear outlet must be cut, in addition to removal of the outer and inner

casing knockouts on furnace.

1. The wall opening measurements for the rear outlet are the follow-

ing.

A. From floor to bottom of wall opening is 14 3/4” (375mm).

B. From the bottom of wall opening to top of wall opening is 8 1/2”

(216mm).

C. Wall opening width is 12 1/8” (308mm).

2. Remove outer casing knockout from outer casing back.

3. Remove inner casing knockout from inner casing.

4. Attach furnace to wall (see Attaching Furnace to Wall).

5. Align clearance holes on 8” x 12” (203mm x 305mm) boot with

screw holes on outer casing back and mark boot to be flush with

wall surface. Remove boot and cut to proper length.

6. Attach 8” x 12” (203mm x 305mm) boot to outer casing back with

(6) #10 x 1/2” (13mm) screws provided.

7. Align clearance holes on 6” x 10” (152mm x 254mm) duct with screw

holes on inner casing and mark duct to be 2 1/4” (57mm) shorter than