Empire Comfort Systems FAW-55SPP User Manual

Page 6

Advertising
background image

12428-6-0408

Page 6

–ANS Z21.45 Assembled Flexible Appliance Connectors of Other Than

All-Metal Constructions

The above connectors may be used if acceptable by the authority having

jurisdiction.
Pressure Testing of the Gas Supply System

1. To check the inlet pressure to the gas valve, a 1/8” (3mm) N.P.T.

plugged tapping, accessible for test gauge connection, must be

placed immediately upstream of the gas supply connection to the

appliance.

2. The appliance and is individual shutoff valve must be disconnected

from the gas supply piping system during any pressure testing of

that system at test pressures in excess of 1/2 psig (3.5 kPa).

3. The appliance must be isolated from the gas supply piping system

by closing its individual manual shutoff valve during any pressure

testing of the gas supply piping system at test pressures equal to or

less than 1/2 psig (3.5 kPa).

Attention! If one of the above procedures results in pressures in excess

of 1/2 psig (14” w.c.) (3.5 kPa) on the appliance gas valve, it will result

in a hazardous condition.
Checking Manifold Pressure

Both Propane and Natural gas valves have a built-in pressure regulator

in the gas valve. Natural gas models will have a manifold pressure of ap-

proximately 4.0” w.c. (.996kPa) at the valve outlet with the inlet pressure

to the valve from a minimum of 5.0” w.c. (1.24kPa). Propane gas models

will have a manifold pressure approximately 10.0” w.c. (2.49kPa) at the

valve outlet with the inlet pressure to the valve from a minimum of 11.0”

w.c. (2.739kPa) for the purpose of input adjustment to a maximum of

13.0” w.c. (3.237kPa).
A 1/8” (3mm) N.P.T. plugged tapping, accessible for test gauge connection,

is located on the outlet side of the gas control.

The built-in regulator comes on at approximately 1/4th pressure and full

on in 10 seconds.

Figure 5

High Altitudes

For altitudes/elevations above 2,000 feet (610m), input ratings should

be reduced at the rate of 4 percent for each 1,000 feet (305m) above sea

level. Canadian High Altitudes for locations having an elevation above

mean sea level between 2,000 feet (610m) and 4,500 feet (1370m), the

manifold pressure is to be decreased from 4.0” w.c. (.996kPa) to 3.2”

(.797kPa) w.c. for Natural Gas and from 10.0” w.c. (2.49kPa) to 8.0” w.c.

(1.992kPa) for Propane Gas.
Piezo Pilot Ignitor Instructions

Depressing the red button completely causes a spark to occur at the pilot. This

is a substitute for a match which requires opening the pilot hole cover.

To light the pilot, it is important that the electrode be 1/8” (3mm) from

the thermocouple. The spark must occur at the point the burner flame

hits the thermocouple. The end of the electrode will be red hot with the

pilot on.

(914mm) plug assembly. Insert 7/8” (22mm) strain relief bushing

into the 7/8” (22mm) hole in the side panel.

Attention! The 7/8” (22mm) strain relief bushing is located within the same

yellow envelope as the Installation Instructions and Owner’s Manual.
Attaching Furnace to Wall

When attaching furnace to the wall remove that portion of baseboard and

molding on the wall which is behind the furnace. Attach furnace to wall,

at the outer casing top, with (2) toggle bolts provided and to floor, at the

outer casing bottom, with (2) #10 x 1 1/2” (38mm) screws provided.
Attention! The screw holes on the outer casing bottom are off-set above the

floor approximately 3/8” (9.5mm). Do not over-tighten screws and distort

the off-set on the outer casing bottom. Distortion of the outer casing bottom

will not allow the lower front panel to be attached to the furnace.
Gas Supply

Check all local codes for requirements, especially for the size and type of

gas supply line required. On Natural gas lines less than 15’ (4.5m) long,

us (1/2” (13mm) pipe; on longer runs, use 3/4” (19mm) iron pipe or equal.

On LP gas lines please consult LP gas supplier.
Installing a New Main Gas Cock

Each appliance should have its own manual gas cock.
A manual main gas cock should be located in the vicinity of the unit. Where

none exists, or where its size or location is not adequate, contact your local

authorized installer for installation or relocation.
Compounds used on threaded joints of gas piping shall be resistant to the

action of liquefied petroleum gases. The gas lines must be checked for

leaks by the installer. This should be done with a soap solution watching

for bubbles on all exposed connections, and if unexposed, a pressure test

should be made.
Never use an exposed flame to check for leaks. Appliance must be

disconnected from piping at inlet of control valve and pipe capped

or plugged for pressure test. Never pressure test with appliance con-

nected; control valve will sustain damage!
A gas valve and ground joint union should be installed in the gas line

upstream of the gas control to aid in servicing. It is required by the Na-

tional Fuel Gas Code that a drip line be installed near the gas inlet. This

should consist of a vertical length of pipe tee connected into the gas line

that is capped on the bottom in which condensation and foreign particles

may collect.

Figure 4

Method of Installing a Tee Fitting Sediment Trap

The use of the following gas connectors is recommended:

–ANS Z21.24 Appliance Connectors of Corrugate Metal Tubing and

Fittings

GAS SUPPLY PIPING

1/8(3mm)NPT PLUGGED HOLE

FOR TEST GAGE

GROUND JOINT UNION

3”(76mm)MINIMUM

MANUAL SHUT-OFF VALVE

GAS SUPPLY
INLET

1/8 (3mm) NPT PLUGGED HOLE

FOR TEST GAGE

GAS

VALVE

TOP VIEW OF VALVE

PRESSURE REGULATOR

OUTLET PRESSURE TAP

GAS OUTLET

PILOT GAS OUTLET

PILOT ADJUSTMENT

SCREW BENEATH

COVER SCREW

MANUAL GAS COCK KNOB

RED RESET BUTTON

INLET PRESSURE TAP

GAS INLET

WRENCH BOSS

VENT

Advertising