Honeywell CHRONOTERM IV T8624D User Manual

Page 6

Advertising
background image

69-1074

6

T8624D CHRONOTHERM

®

IV DELUXE ZONE MULTISTAGE THERMOSTAT

a

The cycle rate for the second stage of heat is adjustable with 6 cph being the factory setting.

(Continued)

Table 3. Thermostat Installer Setup Options.

Installer

Setup Number

(Press Time

key to

Factory-Setting

Other Choices

(Press

or

key to change)

Actual

Select

change)

Display

Description

Display

Description

Setting

Not used

1 thru 4

Heating cycle
rate

a

5

6

Stage 2

3 or 9

3—3 cph used for steam

systems

6—6 cph factory setting for

all stages of system

9—9 cph used for electric

heat

Not used

6 thru 11

System setting
adjustment

12

1

Manual changeover

0 or 2

0—Auto changeover
2—Fixed auto changeover

Adaptive
Intelligent
Recovery™
control

13

0

Adaptive Intelligent
Recovery™ control is
activated (system
starts early so setpoint
is reached by start of
program period)

1

Conventional recovery
(system starts recovery at
programmed time)

Degree tempera-
ture display

14

0

Temperature is
displayed in °F

1

Temperature is displayed
in °C

Not used

15

Clock format

16

0

12-hour clock format

1

24-hour clock format

Not used

17 and 18

Extended fan
operation in
heating

19

0

No extended fan
operation after the call
for heat ends

1

Fan operation is extended
90 seconds after the call for
heat ends.

Extended fan
operation in
cooling

20

0

No extended fan
operation after the call
for cool ends

1

Fan operation is extended
90 seconds after the call for
cool ends.

Not used

21 thru 23

Outdoor temp-
erature display
(models with OT
terminals)

24

0

No outdoor temperature
is displayed

1

Outdoor temperature is
displayed. Needs a
C7089B1000 Outdoor Sensor
to operate.

Not used

25 thru 32