Setting current day and time, T8624d chronotherm, Iv deluxe zone multistage thermostat – Honeywell CHRONOTERM IV T8624D User Manual

Page 7

Advertising
background image

69-1074

7

T8624D CHRONOTHERM

®

IV DELUXE ZONE MULTISTAGE THERMOSTAT

Table 3. Thermostat Installer Setup Options (Continued).

IMPORTANT

Review the settings to confirm that they match
the system. Press Run Program to exit the
Installer Setup. The thermostat has saved the
Installer Setup changes and initiated a reset in
order to operate with the new settings. Be sure to
set the current day and time immediately.

Setting Current Day and Time

Press Set Current Day/Time.

NOTE:

On initial power up or after an extended
power loss, 1:00 pm flashes on the dispaly
until a key is pressed.

Press Day until the current day is displayed.

NOTE:

Sun=Sunday, Mon=Monday,
Tue=Tuesday, Wed=Wednesday,
Thu=Thursday, Fri=Friday, Sat=Saturday.

M10312

Time

Set Program

System

Fan

Run

Program

Hold Temp

Set Current

Day/Time

Set Current

Day/Time

Wake

Leave

Return

Sleep

Day

Heat/Cool

Settings

Daylight

Time

Copy

Mon

PM

Set Day/Time

M10313

Time

Set Program

System

Fan

Run

Program

Hold Temp

Set Current

Day/Time

Wake

Leave

Return

Sleep

Day

Day

Heat/Cool

Settings

Daylight

Time

Copy

PM

Tue

Set Day/Time

Installer

Setup Number

(Press Time

key to

Factory-Setting

Other Choices

(Press

or

key to change)

Actual

Select

change)

Display

Description

Display

Description

Setting

Minimum off time
for the
compressor

33

5

5 minute minimum off
time for the compressor

0 thru 4

Minimum number of minutes
(0 thru 5) the compressor will
be off between calls for the
compressor

Temperature
range stops in
heating

34

90

Highest setpoint
heating can be set to

40 to 89 Temperature range (1°F

increments) heating setpoint
can be set to

Temperature
range stops in
cooling

35

45

Lowest setpoint cooling
can be set to

46 to 99 Temperature range (1°F

increments) cooling setpoint
can be set to

Not used

36

Temperature
display
adjustment

37

0

No difference in
displayed temperature
and actual room
temperature

1 thru 6

1—Display adjusts to 1°F

higher than actual room
temperature

2—Display adjusts to 2°F

higher than actual room
temperature

3—Display adjusts to 3°F

higher than actual room
temperature

4—Display adjusts to 1°F

lower than actual room
temperature

5—Display adjusts to 2°F

lower than actual room
temperature

6—Display adjusts to 3°F

lower than actual room
temperature

Advertising