Warning, D. vent diagrams – Heat & Glo Fireplace Soho24B 2137-900 User Manual

Page 12

Advertising
background image

Heat & Glo • Soho24B • 2137-900 Rev. P • 8/12

12

Figure 5.3

Figure 5.4

1. Top Vent - Horizontal Termination

One Elbow

Two Elbows

V

1

Minimum

H

1

Maximum

Elbow only

1-1/2 ft.

457 mm

1 ft.

305 mm

2-1/2 ft.

762 mm

1-1/2 ft.

457 mm

3-1/2 ft.

1.1 m

2-1/2 ft.

762 mm

5-1/2 ft.

1.7 m

3-1/2 ft.

1.1 m

7-1/2 ft.

2.3 m

4-1/2 ft.

1.4 m

15-1/2 ft.

4.7 m

V

1

+ H

1

= 39 ft. (11.9 m) Maximum

H

1

= 15-1/2 ft. (4.7 m) Maximum

V

1

Minimum

H

1

+ H

2

Maximum

2 - 90º elbows

back to back

Cannot do

6 in

152 mm

1 1/2 ft.

457 mm

1-1/2 ft.

457 mm

2-1/2 ft.

762 mm

2-1/2 ft.

762 mm

4-1/2 ft.

1.4 m

3-1/2 ft.

1.1 m

6-1/2 ft.

1.9 m

5-1/2 ft.

1.7 m

15-1/2 ft.

4.7 m

V

1

+ H

1

+ H

2

= 48 ft. (14.6 m) Maximum

H

1

+ H

2

= 15-1/2 ft. (4.7 m) Maximum

D. Vent Diagrams

Fire Risk. Explosion Risk.
Do NOT pack insulation or other combustibles between ceiling fi restops.
• ALWAYS maintain specifi ed clearances around venting and fi restop systems.
• Install wall shield and ceiling fi restops as specifi ed.
Failure to keep insulation or other material away from vent pipe may cause fi re.

WARNING

H

1

V

1

INSTALLED

HORIZONTALLY

H

1

H

2

V

1