T8601D CHRONOTHERM® IV DELUXE PROGRAMMABLE THERMOSTATS

69-1410—2

6

Table 3. Thermostat Installer Setup Options.

Select

Installer Setup

Number

(Press Time !

key to change)

Factory-Setting

Other Choices

(Press ! or " key to change)

Actual

Setting

Display

Description

Display

Description

Not used

1

Fan operation

a

2

0

Conventional application
where equipment control
fan operation in heat mode

1

Heat pump or electric
heat applications where
thermostat controls fan
operation in heat mode

Not used

3

Heating cycle
rate

4

6

6—6 cph used for

conventional heat.

1, 3 or 9 1—1 cph used for radiant

floor heat, gravity
system

3—3 cph used for hot

water systems or high
efficiency furnaces

9—9 cph used for electric

heat systems

Not used

5 thru 11

System setting
adjustment

12

1

Manual changeover.

0 or 2

0—Auto changeover
2—Auto only

Adaptive
Intelligent
Recovery™
control

13

0

Adaptive Intelligent
Recovery™ control is
activated (system starts
early so setpoint is reached
by start of program period)

1

Conventional recovery
(system starts recovery at
programmed time)

Degree
temperature
display

14

0

Temperature is displayed
in °F

1

Temperature is displayed
in °C

Not used

15

Clock format

16

0

12-hour clock format

1

24-hour clock format

Not used

17 and 18

Extended fan
operation in
heating

a

19

0

No extended fan operation
after the call for heat ends

1

Fan operation is
extended 90 seconds
after the call for heat
ends

Extended fan
operation in
cooling

a

20

0

No extended fan operation
after the call for cool ends

1

Fan operation is
extended 90 seconds
after the call for cool ends

Not used

21 thru 23

Outdoor
temperature
display (select
models)

24

0

No outdoor temperature is
displayed

1

Outdoor temperature is
displayed. Needs a
C7089B1000 Outdoor
Sensor to operate

Not used

25 thru 29

Deadband

30

3

Heating and cooling
setpoints can be set no
closer than 3°F (1.5°C)

4 thru 10 Heating and cooling

setpoints can be set no
closer that chosen value:

4—4°F (2°C)
5—5°F (2.5°C)
6—6°F (3°C)
7—7°F (3.5°C)
8—8°F (4°C)
9—9°F (4.5°C)
10—10°F (5°C)

Not used

31 and 32

Minimum off
time for the
compressor

33

5

5 minute minimum off- time
for the compressor.

0 thru 4 Minimum number of

minutes (0 thru 5) the
compressor is off
between calls for the
compressor