T8601D CHRONOTHERM® IV DELUXE PROGRAMMABLE THERMOSTATS

7

69-1410—2

a

Number 2 must be set to 1 to extend fan operation.

IMPORTANT

Review the settings to confirm that they match
the system. Press Run Program to exit the
Installer Setup. The thermostat has saved the
Installer Setup changes and initiated a reset in
order to operate using the new settings. Be sure
to set the current day and time immediately.

Temperature
range stops in
heating

34

90

Highest heating setpoint
setting.

40 to 89 Temperature range (1°F

increments) of heating
setpoint settings.

Temperature
range stops in
cooling

35

45

Lowest cooling setpoint
setting.

46 to 99 Temperature range (1°F

increments) of cooling
setpoint settings.

Not used

36

Temperature
display
adjustment

37

0

No difference in displayed
temperature and actual
room temperature

3 thru -3 1—Display adjusts to 1°F

higher than actual
room temperature

2—Display adjusts to 2°F

higher than actual
room temperature

3—Display adjusts to 3°F

higher than actual
room temperature

-1—Display adjusts to

1°F lower than actual
room temperature

-2—Display adjusts to

2°F lower than actual
room temperature

-3—Display adjusts to

3°F lower than actual
room temperature

Furnace air
filter timer

43

2

30 days (System run time)

0, 1, 3, 4 0—off

1—10 days
3—60 days
4—120 days
(Time is counted when
heat, cool or fan is
running)

Humidifier pad
monitor

44

0

Off

1, 2, 3 1—90 days

2—189 days
3—365 days

Ultraviolet (UV)
air treatment
system lamp
monitor

45

0

Off

1

1—365 days
(Time is counted by
calendar days in any
mode.)

Table 3. Thermostat Installer Setup Options.

Select

Installer Setup

Number

(Press Time !

key to change)

Factory-Setting

Other Choices

(Press ! or " key to change)

Actual

Setting

Display

Description

Display

Description