Important – Hoshizaki KM-320MAH User Manual

Page 14

Advertising
background image

14

2nd Cycle and after with pump drain

4. Defrost timer stops counting.

Defrost cycle is completed and
freeze cycle starts.

2. Drain timer stops counting.

Pump drain is completed.

5. After the first 5 minutes in freeze cycle.

Ready to complete freeze cycle when float
switch circuit opens.

IMPORTANT

1. Board never accepts defrost completion signal

within the first 2 minutes in defrost cycle.

2. Defrost cycle time is limited to 20 minutes even

if defrost timer does not stop counting.

3. Thermistor reads 48°F (9°C).

Defrost timer starts counting.

IMPORTANT

Board never accepts freeze completion signal
within the first 5 minutes in freeze cycle.

IMPORTANT

Water valve opening is
limited to 6 minutes.

Defrost Timer

Drain Pump

Hot Gas Valve

Defrost
Cycle

Freeze
Cycle

Pump, Fan &
Line Valve

1. Float switch opens and signals to complete

freeze cycle. Drain timer starts counting.

IMPORTANT

Freeze cycle time is limited by the freeze timer
factory setting even if the float switch does not
open.

W

ater V

alv

e

Advertising
This manual is related to the following products: