a) Defrost Control

A thermistor (semiconductor) is used for a defrost control sensor. The resistance varies
depending on the suction line temperatures. The thermistor detects the temperature of
the evaporator outlet to start the defrost timer. No adjustment is required. If necessary,
check for resistance between thermistor leads, and visually check the thermistor
mounting, located on the suction line next to the evaporator outlet.

Temperature (°F) Temperature (°C) Resistance (kΩ)

0

-18

14.401

10

-12

10.613

32

0

6.000

50

10

3.871

70

21

2.474

90

32

1.633

Check a thermistor for resistance by using the following procedure:

1) Disconnect the connector K3 on the board.
2) Remove the thermistor. See "V.H. Removal and Replacement of Thermistor."
3) Immerse the thermistor sensor portion in a glass containing ice and water for 2 or 3

minutes.

4) Check for a resistance between thermistor leads. Normal reading is within 3.5 to 7 kΩ.

Replace the thermistor if it exceeds the normal reading.

b) Defrost Timer

No adjustment is required under normal use, as the defrost timer is adjusted to the
suitable position. However, if necessary when all the ice formed on the evaporator does
not fall into the bin in the harvest cycle, adjust the defrost timer to longer setting by
adjusting the dip switch (No. 1 & 2) on the controller board.

Dip Switch Setting

Time

(seconds)

No. 1

No. 2

OFF

OFF

60

ON

OFF

90

OFF

ON

120

ON

ON

180