N. Adjustment Of Water Regulating Valve – Water-Cooled Model Only

The water regulating valve (also called "water regulator") is factory-adjusted. No
adjustment is required under normal use. Adjust the water regulator, if necessary, using
the following procedure.

1) Attach a pressure gauge to the high-side line of the system. Or prepare a thermometer

to check for the condenser drain temperature.

2) Rotate the adjustment screw by using a flat blade screwdriver, so that the pressure

gauge shows 270 PSIG or the thermometer reads 104 to 115°F, 5 minutes after a
freeze cycle or icemaking process starts. When the pressure exceeds 270 PSIG,
or the condenser drain temperature exceeds 115°F, rotate the adjustment screw
counterclockwise. See Fig. 2.

3) Check that the pressure or the condenser drain temperature holds a stable setting.

Fig. 2

Adjustment Screw

Adjustment Screw

CW – Higher
CCW – Lower

Top View

Advertising