For vertical runs – Heat & Glo Fireplace EVEREST User Manual

Page 17

Advertising
background image

Heat & Glo • Everest • 750-900 Rev. L • 1/06

17

For Vertical Runs

- One ceiling firestop is REQUIRED

at the hole in each ceiling through which the vent passes.

To install firestops for vertical runs that pass through ceilings:

• Position a plumb bob directly over the center of the verti-

cal vent component.

• Mark the ceiling to establish the centerpoint of the vent.

• Drill a hole or drive a nail through this centerpoint.

• Check the floor above for any obstructions, such as wir-

ing or plumbing runs.

• Reposition the fireplace and vent system, if necessary,

to accommodate the ceiling joists and/or obstructions.

• Cut a 10-inch x 10-inch (254mm x 254mm) hole through

the ceiling, using the centerpoint previously marked.

• Frame the hole with framing lumber the same size as the

ceiling joists.

Figure 15. Ceiling Firestop (Ceiling Side)

If the area above the ceiling is NOT an attic, position and
secure the ceiling firestop on the ceiling side of the previously
cut and framed hole.

This shows a ceiling installation.

Figure 14. 10" x 10" Hole & New Framing Members

If the area above the ceiling IS an attic, position and secure
the firestop on top of the previously framed hole.

This shows an attic installation. Keep insulation away from
the vent pipe at least 1 inch (25mm).

Figure 16. Attic Firestop

JOIST

CEILING FIRESTOP

CEILING

NAILS (4 REQUIRED)

CEILING

CEILING FIRESTOP

RAFTER

NAILS (4 REQUIRED)

CEILING

NEW
FRAMING
MEMBERS

EXISTING CEILING
JOISTS

CHIMNEY
HOLE

10" (254 mm)

10" (254mm)

NOTE: There must be NO INSULATION or other
combustibles inside the framed firestop opening.

Figure 13. 10" x 12" Hole and Vent Pipe

To install firestops for horizontal runs that pass through
either interior or exterior walls:

Cut a 12-inch by 10-inch (305mm X 254mm) hole through
the wall. The center of the hole is one (1) inch (25.4mm)
above the center of the horizontal vent pipe.

Position the firestops on both sides of the hole previ-
ously cut and secure the firestops with nails or screws.

The pipe opening of the firestops MUST be placed to-
wards the bottom of the fireplace.

NOTE: There must be NO INSULATION or other
combustibles inside the framed firestop opening.

10"

12"

INTERIOR

WALL SHIELD

Advertising