Occupancy and override – Honeywell ZIO TR71-H User Manual

Page 10

Advertising
background image

ZIO

®

/ZIO PLUS LCD WALL MODULES

63-2719—03

10

Occupancy and Override

I

Ocupancy

and

Override

selection from Wizard Menu

Fig. 17 shows the Occupancy and

Override options in the main

window for standard and

advanced settings. Clicking the Show Advanced Settings

button displays the advanced settings.

NOTES:

1.

The preview at the bottom of the window displays

the occupancy option currently selected.

2.

If an Override option is selected, the Override

softkey displays in the preview. Pressing the Over-

ride softkey cycles through the available override

options.

ENABLE OCCUPANCY OVERRIDE

Clicking the Enable Occupancy Override box enables this

feature and also enables the current Occupancy status (3:00

hours as shown in Fig. 17).

Clicking on the Settings button for the Valid States That You

Can Override section opens the Override to Occupied

Settings dialog box where you can configure values to any

desired number from 0 to 255. To conserve Zio memory,

choose the same Override Type and Timed Override Details

for Occupied, Unoccupied and Standby.

Fig. 17. Occupancy and Override screens.

OCCUPANCY STATUS DISPLAY OPTIONS

Here you select how the override status displays on the LCD.

The options are:

• Show effective occupancy status – LCD shows the actual

occupancy status taking into account the programmable

controller configuration.

• Show occupancy override status – LCD shows the

occupancy override status initiated from the LCD,

independent of the programmable controller configuration.

• Do not show occupancy or override status – LCD does not

show occupancy or override, regardless of what the user

initiates and the programmable controller configuration.

STANDARD SETTINGS

ADVANCED SETTINGS

Advertising
This manual is related to the following products: