/ZIO PLUS LCD WALL MODULES

63-2719—03

8

Fig. 14. Select from the existing library or define enumerated

values.

HIGH/LOW LIMIT PARAMETER LINKING

This option allows for changes to a setpoint's high or low limit

directly at a Zio by linking the high and low limit to a related

setpoint. For example, for an occupied heat parameter, you

could assign the related unoccupied heat setpoint parameter

as the low limit and the occupied cooling setpoint parameter

as the high limit. To assign a setpoint to another setpoint's

high or low limit, click on the Browse button next to the Low

Limit or High Limit field. From the Select Parameter dialog box

you can select the appropriate setpoint.

This feature is an alternative to assigning a numeric value in

the High/Low Limit fields, which require any change be made

in the configuration tool and then loaded to Spyder.

Continue with “Home Screen Options” on page 9.