General Settings

Using Fig. 6 and Table 4 as a guide, configure the General

Settings. An image of the selected model and its capabilities

updates in the display at the bottom of the window.

Fig. 6. General Settings screen.

If you are creating a customized configuration or modifying a

pre-programmed configuration, continue with “Categories and

Parameters” on page 5.

If you are using a pre-programmed configuration as is,

continue with “Preview” on page 17.

Categories and Parameters

I

Categories

and

Parameters selection from

Wizard Menu

The categories and parameters menu item allows you to

create, edit, and delete categories and parameters.

ADDING A CATEGORY

Fig. 7 shows the categories listed in tree format in the main

window where you can add, edit, or remove them. In the

bottom pane, Category Preview (at the bottom of Fig. 7)

shows the current selected item.

Clicking the Add Category button displays a details pane

below the category and parameter tree as shown in Fig. 8.

NOTE: You can use the Remove button to delete unused

categories and parameters to free up memory

space.

Fig. 7. Category Preview.

CATEGORY DETAILS

When you select a category from the Categories tree list and

click the Edit button, a details pane displays for that category

(see Fig. 8 on page 6).

Here you can enter a category name and description. The

number of parameters in this category are shown. The

description text you enter is loaded to the controller but cannot

be seen in the preview.

Table 4. General Settings.

Item

Function/Use

Block Name

The wizard displays S-Bus Wall Module.

Wall Module

Type

Select the appropriate type (Temperature

Only, or a combination of Temperature,

and/or Humidity) from the drop down list.

Model Options

Click LCD Display.

Select Model

Select the appropriate model, TR70,

TR71, or TR75, from the drop down list.

Wall Module

Address

Select a unique address for each TR70

Series devices connected to the Spyder.

TR70 can be set from 1-5 and TR71/

TR75s can be set from 1-10. The

address selected must match the

address setting at the wall module (using

the rotary switches). If setting the TR71/

TR75 rotary switch to 0, set the address

to 10 in the configuration tool.

Time Display

Format

Select 12 or 24 hour format.