Honeywell ZIO TR71-H User Manual

Page 7

Advertising
background image

ZIO

®

/ZIO PLUS LCD WALL MODULES

7

63-2719—03

PARAMETER TYPES AND LIMITS

See Fig. 12 for an illustration of the Parameter Type drop

down list. There is a limit to the number of parameters that can

be configured. In addition to the parameter limit, there is also a

memory limit (see “Memory Usage” on page 4).

Fig. 12. Parameter Type selection.

The individual parameters are defined as:

— Controller Value

• These are read-only inputs to the wall module from

the controller and include system status and

occupancy status, if configured. Controller Value

parameters take up less memory than other

parameters.

— Value From Wall Module

• These are outputs from the wall module such as

room setpoint.

— Network Setpoints

• A network setpoint is a network variable from the

controller that you want to view and change at the

wall module.

— Sensors

• 2 sensors (Temperature and Humidity)

• 2 Sensor Offset Values (temperature and humidity)

See Table 5 for the individual parameter maximums.

IMPORTANT

You can not maximize all of these parameters

together. The size of the data files limits the total

number. See the memory usage tool by clicking on

the Memory Usage Details button in the left pane of

the Configuration Wizard.

* The TR71/TR75 may vary from these capacity numbers

depending on label names, parameter limit reuse, and other

devices that Zio interacts with on the Sylk bus.

NOTE: Network Variables need to be linked to the appropri-

ate S-Bus wall module’s function block slots. See

“Link Slots on the Wire Sheet” on page 18 for details.

PARAMETER OPTIONS

The TR71 and TR75 support additional parameter control.

See Table 1 on page 2 for details.

ENUMERATED VALUES

Meaningful enumerated values can be displayed using the

Enumerated option.

From the Add/Edit parameter window check the Enumerated

box and click on the Define Enum Range as shown in Fig. 13.

Fig. 13. Click on the Enumerated Checkbox, then the Define

Enum Range button.

Once in the Zio Enum Library dialog box (Fig. 14), click on the

dropdown to see pre-defined facets or define your own. For

more detailed information see the online help in the

Configuration Wizard.

Table 5. TR70 Series Parameter Capacity Guidelines.*

Parameter Type

TR70

TR71

TR75

Controller Value

30

95

250

Value From Wall Module

20

50

180

Network Setpoints

10

50

125

Advertising
This manual is related to the following products: