TR70 SERIES FEATURES

* A maximum of four Zios may be wired on a single Sylk bus,

with no more than one TR70 per bus.

Compatibility

The TR70 Series LCD Wall Modules operate with the Sylk

Enhanced Spyder Controller or the Sylk Enhanced

ComfortPoint Controller. The table below provides

compatibility information for each model. The TR71/TR75 can

replace a TR70 in an installation where an upgrade to WEBs-

AX or Spyder or reprogramming is not desired. Features like

scheduling, additional memory, etc. will not be available.

Likewise, a TR71 can be replaced by another TR71 or TR75

without reprogramming required. A TR75 can only be

replaced with a TR75 where no reprogramming is desired.

INITIAL POWER-UP

IMPORTANT

1. Make sure the TR70 Series wall module is properly

mounted and properly wired and connected to the

programmable controller.

2. Refer to the Zio™ LCD Wall Modules TR70 Series

with Sylk™ Bus – Installation Instructions, form 62-

0271, for specific installation requirements.

Upon initial power-up before configuring the wall module, the

LCD screen displays the phrase “PLEASE LOAd” in the Label/

Value area of Fig. 2. This phrase alternates with any onboard

sensor display such as temperature. The TR71/TR75 also

display the firmware revision number, model number and Sylk

bus address as shown in Fig. 27.

Fig. 2 illustrates all the possible LCD Wall Module display

elements. Only those elements pertinent to the current

configuration and status actually display.

Fig. 2. TR70 Series Wall Module - LCD screen.

* The new Spyder tool (6.0 or greater) assumes the latest Spyder capability. At download, the Tool reads the brand/model of the

connected Spyder and determines if it matches the features on the wire sheet. If old or new Spyder is programmed with aTR70,

it can be physically replaced with a TR71 or TR75.

Table 1. TR70 Series Features.

Features

Zio

TR70

Zio

TR71

Zio Plus

TR75

Scheduling

x

Parameter Memory (bytes)

1K

2K

4.9K

Up to four Zios on Sylk

x*

x

x

Enumerated Values

x

x

Setpoint Limits as NVs – linking

now possible

x

x

System and Fan command as NVs

x

x

Password protection

x

x

Firmware version/model visible on

display

x

x

0.5 and 5 value increments

x

x

"-" and "/" characters in parameter

names

x

x

SYSTEM

STATUS

AREA

FAN

INFORMATION
SOFTKEY

LABELS

LABEL/

VALUE

(8 CHAR.)

CURRENT

DISPLAYED

VALUE

OCCUPANCY

STATUS

ENGINEERING

UNITS

OVERRIDE

INFORMATION

M27353

Table 2. Compatibility.*

Scenari

o

Spyde

r Tool

Spyder

Firmware

Compatible

?

Zio TR70/TR71/TR75*

What can be done?

1

5.200

+

Latest

YES

New TR71/75 functionality

available (if TR70 is present,

then only TR70

functionality)

Ideal scenario

2

5.200

+

Old

YES

Only with TR70 functionality

(TR71/75 can be used, but

only TR70 functionality will

be there)

Spyder firmware can be upgraded (this becomes scenario

1)

3

< 5.18 Latest

NO

Tool does not recognize the

new Spyder

Spyder Tool can be upgraded (this becomes scenario 1)

Spyder firmware can be downgraded (this becomes

scenario 4)

4

< 5.18 Old

YES

Only with TR70 functionality

(TR71/75 can be used, but

only TR70 functionality will

be there)

Both Spyder firmware and Tool can be upgraded (this

becomes scenario 1)

Spyder Tool can be upgraded (this becomes scenario 2)

Spyder firmware can be upgraded (this becomes scenario

3)