Setup and configuration, Initial setup and configuration, Selecting the wall module – Honeywell ZIO TR71-H User Manual

Page 3: Tr71/tr75 labels, Navigation and memory usage, Confirm bus address setting, Navigation

Advertising
background image

ZIO

®

/ZIO PLUS LCD WALL MODULES

3

63-2719—03

SETUP AND CONFIGURATION

Initial Setup and Configuration

Once the wall module is wired to the controller, you configure

the wall module using the PC-based, Niagara Workbench

Tool. Refer to the applicable programmable controller User’s

Guide. (Refer to the Honeywell Spyder User’s Guide, form 63-

2662, or the ComfortPoint Programmable Controller User’s

Guide, form 63-2663, depending on the programmable

controller used.) This tool is used to configure the wall module

for either the Spyder or the ComfortPoint programmable

controller.

Confirm Bus Address Setting

Check to ensure that the Wall Module’s bus address dial

(located on the back of the module) is set to match the setting

in the configuration tool. TR70 models can be set from 1–5

and TR71/TR75 can be set from 1–10 (0 on the Zio address

dial is equal to 10 in the configuration tool). The address must

be different for each device on the Sylk bus. Up to four Zios

per Spyder are allowed with any combination of TR71/TR75s

and up to three Zios are allowed if one or more is a TR70

model.

Selecting the Wall Module

You will use the Sylk S-Bus wall module function block from

the Palette’s Built-In folder (see Fig. 3). This configuration has

nothing programmed except the room temperature parameter

and occupancy status.

1. Add the Sylk S-Bus Wall Module function block to the

wire sheet via a left click, drag, and drop. See callout 1

in Fig. 3.

2. Right click on the S-Bus Wall Module function block to

open the Configuration Properties menu. See callout 2

in Fig. 3.

3. Left click on the title, Configuration Properties. This

action starts the Configuration Wizard. The Configura-

tion Wizard steps (see Fig. 5 on page 4) are used to

configure the wall module.

Fig. 3. Niagara Tool Interface - S-Bus wall module selection.

TR71/TR75 Labels

The TR71/TR75 allows the use of the following special

characters in label fields such as Categories and Parameter

Names: underscore ( _ ) to insert a space, hyphen ( - ), and

forward slash ( / ). The TR70 allows use of the underscore

( _ ) character to insert a space.

Navigation and Memory Usage

The Honeywell Spyder Tool uses an intuitive, window-based

interface. A Help button on each screen provides assistance

with any entry or process.
IMPORTANT

Use the Help button to display context specific help

for the current window or pane display. See the lower

left corner of Fig. 6 on page 5 for the location of the

Help button.

NOTE: At any time, clicking the Preview button (lower left of

main window, see Fig. 6 on page 5) displays the

updated wall module LCD as a pop-up. Preview sim-

ulates the actual wall module interface and allows

you to verify the operation of the current configura-

tion of the wall module. See “Preview” on page 16.

Navigation

Table 3 describes the navigation buttons at the bottom of the

wall module window. See the bottom of Fig. 7 on page 5 for

the location of these buttons. Buttons are greyed when

unavailable.

VAV_Temp_NoBal_NwOvrdTime

VAV_Temp_MnMxBal_NwOvrdTime

VAV_Temp_KfacBal_NwOvrdTime

VAV_Temp_NoBal_AllOverride

SBusWallModule

M27820

RIGHT CLICK

DRAG

AND

DROP

1

2

Table 3. Navigation Buttons.

Item

Function/Use

Help

When clicked, this button provides context sensitive

help for the currently selected item or parameter.

Preview When clicked, this button displays the updated wall

module LCD in a pop-up window pane. Preview is

fully interactive and simulates the actual wall

module interface as currently configured (see

“Preview” on page 16 for details).

Save to

Library

For new custom configurations and standard

configurations.

Clicking the button opens the Save to Library

screen (shown in Fig. 25 on page 17). This action

allows you to save the entire current wall module

configuration.

The Save to Library button is disabled until you

change the configuration (application). After a

change is made, you can save the new

configuration into the library under a new name.

Back

Takes you backward one step in the wizard

interface.

Next

Takes you forward one step in the wizard interface.

Finish

Clicking this button commits all changes to the

database, closes the Configuration Wizard, and

returns you to the wire sheet.

Cancel

Prompts you with a confirmation message.

If you reply Yes, then all selections/entries made

since the Save to Library button or Finish button

was last pressed are ignored, and the wizard

interface quits.