Hrv200plus installation instructions – Hearth and Home Technologies Heat Recovery Ventilator HRV200PLUS User Manual

Page 12

Advertising
background image

12

4034-102 Rev F

02/04

HRV200PLUS INSTALLATION INSTRUCTIONS

b. Install Fresh Air Supply Ducting

The inner and outer liners of the insulated duct must be clamped

to the sleeve of the weatherhood as close to the outside as

possible and to the plastic inlet port on the HRV200PLUS. It is

very important that the fresh air intake line be given special

attention to make sure it is well sealed. A good bead (½”) of

high quality caulking (preferably acoustical sealant) will seal the

inner duct to both the HRV port and the weatherhood prior to

clamping.
To minimize air flow restriction, the flexible insulated duct (if

used) that connects the outside weatherhood to the

HRV200PLUS should be stretched tightly and be as short as

possible.
Twisting or folding the duct will severely restrict air flow. See

Figure 2 for the recommended connection of insulated ducts to

the outside weatherhood and the HRV200PLUS.
Ducting must be installed in accordance with local codes.

2. Warmside Air Supply -

Heated fresh air from the HRV into the

living area

Duct Materials: Insulated Metal Air Duct - rigid or flexible, 200°F rated

CoolVent™ Flexible Pipe may be used.
Duct Adapter - (Simplified Installation)
Diffusers or Grilles - 200°F rated (Dedicated Installation)

Note:

Due to elevated temperatures in the fresh air supply duct:

• Use only ducting materials rated for use at or above 200°F
• Do not use plastic duct or terminations rated below 200°F.
• Do not connect fresh air supply duct into the return duct work of the furnace. Hot air stream could damage exposed

components in the furnace return cabinet.

• WHEN USING THE EXISTING DUCT WORK FOR AIR DISTRIBUTION, ALWAYS CONNECT TO THE SUPPLY DUCT

WORK DOWNSTREAM OF THE CENTRAL FURNACE OR AIR HANDLER.

a. Duct the Warmside Air Supply

The HRV200PLUS recovers heat from the fireplace normally wasted in the flue. This means that the temperatures achieved

in the fresh air stream to the home will typically be 100°F hotter than the outdoor ambient temperature. Under some operating

conditions, the temperature inside the fresh air supply duct could be as high as 200°F.
The fresh air should be supplied to all living areas and bedrooms, excluding bathrooms, kitchens and utility areas.

The fresh air supply may be delivered to the home through a dedicated duct system when:

1) No central forced air system exists,
2) The HRV200PLUS is not in close proximity to the central supply air ducts or
3) Heating load design factors favor dedicated supply registers.

When dedicated supply grilles are used, grilles that diffuse the air comfortably from high wall or ceiling locations are

recommended.
In homes with a forced air distribution system, direct connection to the furnace supply duct work is the preferred method for

supplying fresh air from the HRV200PLUS. This will ensure fresh air is delivered evenly throughout the house and utilizes the

existing duct work infrastructure.
When connected to the furnace supply air duct work, the duct adapter should be installed to insure reliable air flow and stable

operation of the HRV200PLUS. The duct adapter is designed to minimize the effects of static pressure in the duct regardless

of the furnace blower speed selection and allows for fast, easy and airtight connections.
Remember to check the air flow balance of the HRV200PLUS with the furnace fan both on and off to determine that it does not

imbalance the ventilator more than 10%.

Figure 2

Advertising