HRV200PLUS INSTALLATION INSTRUCTIONS

4. Chase/Termination Installation

Figure 12 and Table 1 specify minimum vent heights

for various pitched roofs.
These vent heights are necessary for safety and do

not ensure draft-free operation. Trees, buildings,

adjoining roof lines, adverse conditions, etc. may create

a need for a taller vent should down drafting occur.

Figure 12 - Vent Height for Vertical Termination

Roof Pitch

H (Min.) Ft.

Flat to 6/12 ................................................ 1.0

6/12 to 7/12 ............................................... 1.25

Over 7/12 to 8/12 ...................................... 1.5

Over 8/12 to 9/12 ...................................... 2.0

Over 9/12 to 10/12 .................................... 2.5

Over 10/12 to 11/12 .................................. 3.25

Over 11/12 to 12/12 .................................. 4.0

Over 12/12 to 14/12 .................................. 5.0

Over 14/12 to 16/12 .................................. 6.0

Over 16/12 to 18/12 .................................. 7.0

Over 18/12 to 20/12 .................................. 7.5

Over 20/12 to 21/12 .................................. 8.0

Vent Height

Table 1