Remote air-cooled condenser – Heatcraft Refrigeration Products REMOTE AIR-COOLEDCONDENSER 2500018 User Manual

Page 3

Advertising
background image

The condenser should be located no closer than four feet from

any wall or other obstruction to provide sufficient clearance

for air entrance. Do not attach ductwork to the coil inlet or fan

outlet. Care should be taken to avoid air recirculation conditions

that can be caused by sight screening, walls, etc. Keep unit fan

discharge away from any building air intakes.

Space and Location Requirements

The most important aspect in selecting a location for air-cooled

equipment is a supply of ambient air to the condenser and the

adequate removal of heated air from the condenser area. If

the requirement for adequate air circulation is not adhered to,

higher head pressures will result, creating poor operation and

possible failure of equipment. Units must not be located in the

vicinity of steam, hot air or fume exhausts.

Walls or Obstructions

The unit should be located so that air may circulate freely and

not be recirculated. For proper air flow and access, all sides of

the unit should be a minimum of the width of the unit away

from any wall or obstruction. It is preferable for this distance

be increased whenever possible.

Care should be taken to see that ample room is left for

maintenance through access doors and panels. Overhead

obstructions are not permitted. When the unit is in an area

where it is enclosed by three walls the unit must be installed

as indicated for units in a pit.

Units In Pits

The top of the unit should be level with the top of the pit and

side distance increased to two times the width of the unit.

If the top of the unit is not level with the top of pit, discharge

cones or stacks must be used to raise discharge air to the top

of the pit. This is a minimum requirement.

Multiple Units

For units placed side by side, the minimum distance between

units is the width of the largest unit. If units are placed end to

end, the minimum distance between units is four feet.

Decorative Fences

Fences must have 50 percent free area, with a one-foot undercut,

a minimum clearance equal to the width of the unit and must

not exceed the height of the unit. If these requirements are not

met, unit must be installed as indicated for units in pits.

Sound and Vibration

Units should be installed away from occupied spaces

to reduce the transmission of sound and vibration

to occupied spaces. Units should be mounted over

corridors, utility areas, rest rooms and other auxiliary areas

where high levels of sound are not an important factor.

Sound and structural consultants should be retained

for recommendations.

The refrigerant piping should be flexible enough to

prevent the transmission of noise and vibration from the

unit into the building. If the refrigerant lines are to be

suspended from the structure of the building, isolation

hangers should be used to prevent the transmission

of vibration.

Where piping passes through a wall, it is advisable to pack

fiberglass and sealing compound around the lines to minimize

vibration and retain flexibility in the lines. The unit needs to

be secured in its final location. Holes are provided in the base

runner for this purpose.

Remote Air-Cooled Condenser Installation and Operations Manual, August 007

3

Remote Air-Cooled Condenser

*W = Total width of the condenser.

Advertising