Start Up

Check for proper fan rotation. Air is drawn through the coil on

all units. Be sure the fans turn freely. Rotation of the motors and

blades should be in a clockwise direction looking at the unit

from the blade side. On three-phase units, it may be necessary

to reverse two of the three power leads to the unit.

NOTE: The manifold assembly is not designed to support

field piping� Any damages to the condenser due to

excessive weight, pressure or vibration will not be covered

by standard warranty�

Operation

Winter Operation Head Pressure Control

The capacity of an air-cooled condenser varies with the

difference between the entering air dry bulb temperature and

the condensing temperature of the refrigerant.

Because air temperature in some regions varies as much as

100 degrees from summer to winter, some means must be

employed to keep the condensing temperature sufficiently

high to ensure proper operation of the refrigerant expansion

valve during low ambient operation, and also allow sufficient

capacity so that excessively high condensing temperatures do

not result during high ambient conditions. The low limit of the

head pressure is dependent upon the required pressure drop

across the thermostatic expansion valve.

For normal air conditioning applications, head pressure should

be maintained above a condensing temperature corresponding

to 90°F. This corresponds to a normal lower limit of about 60°F

ambient air. Because air conditioning is not normally required

at these lower ambient temperatures, condenser head pressure

control may not always be necessary.

However, for those applications below 60°F ambient air

temperature, two methods of condenser head pressure control

are available to meet specific job requirements and engineer/

owner preference: Fan Cycling, Variable Speed and Flooded

Head Pressure Control (FHP)�

Fan Cycling Method

This is an automatic winter control method and will maintain

a condensing pressure within reasonable limits by cycling fan

motors in response to outside air temperature entering the

condensing coil. When voltage other than 30/08 is supplied

to the unit, a transformer will be provided for field installation.

Electrical protection must be provided for this transformer.

Fan Cycling Operation and Installation

The fan cycling control package consists of a weather-tight

enclosure with motor starting contactor(s), as required, and

thermostat(s). The contactor coil is 4 volts, 115 volts or 40

volts as ordered. The thermostats and contactors are wired as

shown on Diagrams 3 and 5.

Factory-installed packages are mounted on the unit and have

all motor connections completed. Field wiring consists of

connecting this panel to a power supply and fused disconnect(s)

together with the control circuit to the contactor coils.

Fan cycling is suitable for outside temperatures above those

shown in Table 4. The thermostat should be field set to shut

off the fan when the condensing temperature is reduced to

approximately 90°F.

Where operation at ambients below the range shown on

Table 4 were required, FHP must be added.

Table 5 lists approximate settings for several system T.D.’s. These

settings are approximate as they do not take into account

variations in load.

NOTE: Fans closest to the headers should not be cycled

on standard temperature or pressure controls� Dramatic

temperature and pressure changes at the headers as a

result of fan action can result in possible tube failure� Fan

motors are designed for continuous duty operation� Fan

cycling controls should be adjusted to maintain a minimum

of five (5) minutes on and five (5) minutes off� Short cycling

of fans may result in a premature failure of motor and/or

fan blade�

Variable Speed

Condenser head pressure control is provided by varying the

air flow through the condenser by changing the RPM of the

condenser fan. This control package is offered in combination

with ambient fan cycling. The fan motor next to the header

end of the condenser is the variable speed fan. The remainder

8

Part # 500018

Installation and Operations Manual

Model

Design T.D.

30°F

5°F

0°F

15°F

-fan units

45

55

65

70

3-fan units

30

40

50

60

Table 4�

Minimum Ambient for Fan Cycling

Model

Design T.D. (°F)

Thermostat Settings

T1

T

-fan units

30

55

-

5

60

-

0

65

-

3-fan units

30

60

45

5

65

50

0

75

55

15

75

65

Table 5�

Fan Cycling Thermostat Settings