Leg Assembly for Horizontal Airflow Installation

(Models 024-133; 5-26)

Remove bolts securing condenser to skid.
Remove item 1 and attach to rear of bottom leg (item A)

to complete mounting base. Item  is not required in the

horizontal discharge application and may be discarded.
Condenser can be hoisted by the 1-1/” holes in

leg assemblies.

Typical Piping Arrangements

Figure 7 illustrates a typical piping arrangement with

a remote condenser located at a higher elevation, common

when the condenser is on a roof and the compressor and

receiver are on grade level or in a basement equipment

room.

In this case, the design of the discharge line is very critical. If

properly sized for full load conditions, the gas velocity might

be too low at reduced loads to carry oil through the discharge

line and condenser coil. Reducing the discharge line size would

increase the gas velocity sufficiently at reduced load conditions;

however, when operating at full load, the line would be greatly

undersized and create an excessive refrigerant pressure drop.

1.
.

3.

This condition can be overcome in one of two following

ways:

The discharge line may be properly sized for the desired

pressure drop at full load conditions and an oil separator

installed at the bottom of the trap in the discharge line from

the compressor.
A double riser discharge line may be used as shown

in Figure 8. Line A should be sized to carry the oil

at minimum load conditions and Line B should

be sized so that at full load conditions, both lines would have

sufficient flow velocity to carry the oil to the condenser.

For more complete information, please refer to the ASHRAE

Handbook on Systems.

NOTES:

All oil traps are to be as short in radius as possible�

Common practice is to fabricate the trap using three

90-degree ells�
Pressure relief valves are recommended at the condenser

to protect the coil�
A drain line check valve is recommended for applications

where the condenser may be at a lower temperature

than the receiver�

See Tables 1, 2, and 3 for discharge and liquid drain line size

recommendations for remote condenser selections.

Installation, Refrigerant Piping

Install piping according to standard accepted refrigeration

practice. The following recommendations should be adhered

to:

Use only refrigeration-grade copper tubing.
Soft solder joints are not acceptable.
Put dry nitrogen through lines while brazing.
Do not leave dehydrated piping or components open to the

atmosphere any longer than is necessary.

1.

.

1�

2�

3�

1.
.
3.
4.

Remote Air-Cooled Condenser Installation and Operations Manual, August 007

5

Remote Air-Cooled Condenser

Figure 6. Leg assembly (horizontal airflow, models 024-133; 5-26)

Figure 7

Figure 8