C. vent termination – Heat & Glo Fireplace 8000TRD User Manual

Page 23

Advertising
background image

23

Figure 29. Ceiling Firestop (Ceiling Side)

If the area above the ceiling is NOT an attic, position and
secure the ceiling firestop on the ceiling side of the previously
cut and framed hole.

If the area above the ceiling IS an attic, position and secure
the firestop on top of the previously framed hole.

NOTE: Keep insulation away from the vent pipe at least
1 inch (25mm).

Figure 30. Attic Firestop

JOIST

CEILING FIRESTOP

CEILING

NAILS (4 REQUIRED)

CEILING

CEILING FIRESTOP

RAFTER

NAILS (4 REQUIRED)

NOTE: There must be NO INSULATION or other
combustibles inside the framed firestop opening.

!

C. Vent Termination

For Horizontal Terminations - To attach and secure the
termination to the last section of horizontal vent:

• Rotate and interlock the ends as described at the begin-

ning of the Installing Vent Components section.

• The termination kit should pass through the wall firestops

from the exterior of the building.

• Adjust the termination cap to its final exterior position on

the building.

WARNING: THE TERMINATION CAP MUST BE
POSITIONED SO THAT THE ARROW IS
POINTING UP.

For trapezoidal cap termination kits:

• Using screws secure the cap to the exterior wall through

the flanges in the cap.

Figure 31. Trapezoid Termination Caps

!

WARNING: THE BOTTOM OF THE VENT
TERMINATION CAP MUST BE A MINIMUM

OF 12 INCHES (305 MM) ABOVE GROUND LEVEL
(GRADE). THE TOP OF THE CAP MUST BE A MIN-
IMUM OF 18 INCHES (457 MM) BELOW COMBUS-
TIBLE MATERIAL, SUCH AS A DECK. THE SIDE
OF THE CAP MUST BE A MINIMUM OF 6 INCHES
(152 MM) AWAY FROM A PARALLEL OUTSIDE
WALL. VENTING TERMINALS SHALL NOT BE RE-
CESSED INTO A WALL OR SIDING. SEE THE FOL-
LOWING DIAGRAM FOR VENT TERMINATION
CLEARANCES.

TRAPEZOID CAP TERMINATION

7 1/4"

(184mm)