D. mantel and wall projections – Heat & Glo Fireplace 8000TV-OAK User Manual

Page 21

Advertising
background image

Heat & Glo • 8000TV-OAK, 8000TV-OAK-IPI, 8000TVLP-OAKIPI • 2058-900 Rev. N • 11/08

21

D. Mantel and Wall Projections

WARNING! Risk of Fire! Comply with all minimum clear-
ances as specifi ed. Framing or fi nishing material closer than
the minimums listed must be constructed entirely of noncom-
bustible materials (i.e., steel studs, concrete board, etc).

Figure 5.3 Minimum Vertical and Maximum Horizontal

Dimensions of Combustibles

Figure 5.4 Combustible Mantel Leg or Wall Projections

(Acceptable on both sides of opening)

Combustible Mantels

Combustible Mantel Legs or Wall Projections

1/2 INCH

(13 mm)

32 IN.

(813 mm)

TOP OF HOOD

12 IN.

(305 mm)

NON-COMBUSTIBLE

MATERIAL ONLY

13 IN.

(330 mm)

CEILING

TOP FRONT EDGE OF FIREPLACE

Note: Clearance from opening
to perpendicular wall.

1 in.
MIN.

3 in.

MIN.

3 ft.

MAX.

TOP VIEW