Slide the gas insert into place, and
position any excess flexible vent pipe back
up into the chimney. Attach the pipe-to-
cap adaptor to the termination cap and
to the top of the flexible vent pipe and set
the cap in place at the top of the chimney.
See Figures 4 and 5.

CAUTION: TO AVOID DOWNDRAFTS
AND/OR COLD AIR PROBLEMS, IT IS
RECOMMENDED TO SEAL OFF THE
AREA BETWEEN THE TERMINATION
CAP AND THE TOP OF THE SOLID-
FUEL CHIMNEY OPENING INTO
WHICH THE VENT CAP HAS BEEN IN-
STALLED.

WHEN USING THE LINK-DV4-30 VENT
SYSTEM, IT IS REQUIRED TO SEAL
AROUND THE FLEXIBLE VENT PIPES
IN THE DAMPER AREA. SEE FIGURE
5. USE FIBERGLASS INSULATION OR
OTHER SUITABLE NON-COMBUSTI-
BLE MATERIAL.

WARNING: MAJOR U.S.
BUILDING CODES SPECIFY

MINIMUM CHIMNEY AND/OR VENT
HEIGHT ABOVE THE ROOF TOP.
THESE MINIMUM HEIGHTS ARE
NECESSARY IN THE INTEREST OF
SAFETY. SEE THE FOLLOWING
DIAGRAM FOR MINIMUM HEIGHTS,
PROVIDED THE TERMINATION CAP
IS AT LEAST 2-FEET FROM A VER-
TICAL WALL AND 2-FEET BELOW
A HORIZONTAL OVERHANG.

NOTE: This also pertains to vertical vent
systems installed on the outside of the
building.

Roof Pitch

H (min.) ft.

flat to 6/12

1.0

6/12 to 7/12

1.25

over 7/12 to 8/12

1.5

over 8/12 to 9/12

2.0

over 9/12 to 10/12

2.5

over 10/12 to 11/12

3.25

over 11/12 to 12/12

4.0

over 12/12 to 14/12

5.0

over 14/12 to 16/12

6.0

over 16/12 to 18/12

7.0

over 18/12 to 20/12

7.5

over 20/12 to 21/12

8.0

Figure 3. Minimum Height from Roof to Lowest
Discharge Opening

HORIZONTAL OVERHANG

VERTICAL WALL

TERMINATION CAP

12

X

ROOF PITCH IS X/ 12

LOWEST
DISCHARGE
OPENING

H (MIN.) - MINIMUM HEIGHT FROM ROOF
TO LOWEST DISCHARGE OPENING

2 FT.
MIN.

2 FT. MIN.