Step 5. Gas Pressure Requirements

Pressure requirements for these gas appliances are shown
in the table below.

Pressure

Natural Gas

Propane

Minimum

5.0 inches

11.0 inches

Inlet Pressure

w.c.

w.c.

Maximum Inlet

14.0 inches

14.0 inches

Gas Pressure

w.c.

w.c.

Manifold

3.5 inches

10.0 inches

Pressure

w.c.

w.c.

Inlet and outlet pressure taps are provided on the front face
of the gas control for a test gauge connection to measure
the manifold pressure. Use a small flat blade screwdriver to
crack open the screw in the center of the tap. Position a
rubber hose over the tap to obtain the pressure reading.

THE FIREPLACE AND ITS INDIVIDUAL SHUT-OFF
VALVE MUST BE DISCONNECTED FROM THE GAS
SUPPLY PIPING SYSTEM AND ISOLATED DURING ANY
PRESSURE TESTING OF THE SYSTEM AT TEST
PRESSURES EQUAL TO OR IN EXCESS OF ONE-HALF
(1/2) PSIG (3.5 KPA).

Step 6. Wiring the Fireplace

NOTE: Electrical wiring must be installed by a li-
censed electrician.

CAUTION: DISCONNECT REMOTE CONTROLS IF AB-
SENT FOR EXTENDED TIME PERIODS. THIS WILL PRE-
VENT ACCIDENTAL APPLIANCE OPERATION.

For Standing Pilot Ignition Wiring
Appliance Requirements

This appliance DOES NOT require 110-120 VAC to operate.

Models FB-Grand and FB-IN require 110-120 VAC if op-

tional blower is added to the system.

WARNING: DO NOT CONNECT 110-120 VAC TO
THE GAS CONTROL VALVE OR THE APPLI-
ANCE WILL MALFUNCTION AND THE VALVE
WILL BE DESTROYED
.

!

Figure 8.

Standing Pilot Ignition Wiring Diagram

THERMOCOUPLE

GAS

VALVE

OPTIONAL WALL SWITCH

THERMOSTAT OR REMOTE

ON

OFF

ROCKER

SWITCH

THERMOPILE

WHITE T2

RED T1

!

Wall Switch

Position the wall switch in the desired position on a wall.
Run a maximum of 25 feet (7.8 m) or less length of 18
A.W.G. minimum wire and connect it to the fireplace valve
pigtails.

WARNING: DO NOT CONNECT 110-120 VAC
TO THE WALL SWITCH OR THE CONTROL
VALVE WILL BE DESTROYED.

CAUTION: LABEL ALL WIRES PRIOR TO DISCONNEC-
TION WHEN SERVICING CONTROLS. WIRING ERRORS
CAN CAUSE IMPROPER AND DANGEROUS OPERATION.
VERIFY PROPER OPERATION AFTER SERVICING.