Relay module, Optional) continued, Wiring details – Honeywell 96D User Manual

Page 23

Advertising
background image

Manning AirAlert-96d Gas Monitor

19073 AIRALERT96D 05/2006 Prelim REVC Copyright © 2006 Honeywell Analytics. All Rights Reserved.

23

10

Relay Module

(optional) continued

Wiring Details

Power Supply Cable

14 AWG stranded cable or larger (see your network
diagram provided by Honeywell Analytics sales
department).

Communication Cable

24 AWG twisted pair (Belden # 9841 or equivalent).

Figure 11. Relay Module PCB

Power

Tx Modbus

Normally
open

Normally
closed

3+5
4+6

1+3
2+4

6

4

2

5

3

1

RC

R

EOL1

Relay Outputs (J1-J8)
5A, 30 Vdc or 120 Vac (resistive load)

V+

V-

SHLD

A

B

J10

J10

J8

J7

J2

J1

From “B” terminal of controller
to “B” terminal of next device

From “A” terminal of controller
to “A” terminal of next device

From +24VDC terminal

of power supply

From Ground terminal

of power supply

NO

NC

NO

NC

Relay 2

NO

NC

Relay 3

Relay 1

NO

NC

Relay 4

NO

NC

NO

NC

Relay 6

NO

NC

Relay 7

Relay 5

NO

NC

Relay 8

End of Line Resistor
On the last device of the
communication network,
a jumper must be
installed as shown.

Power and TX
status LEDs

1
2
3
4

off

DIP switches