D. frame the fireplace, C. sidewalls/surrounds – Hearth and Home Technologies BIR42-B User Manual

Page 20

Advertising
background image

20

D. Frame the Fireplace

Figure 6.4 shows typical framing using combustible materials (2x4 lumber shown).
• Observe all required air space clearances to combustible materials as shown in Figure 6.2.

18 1/2 in.

[470 mm]

19 3/4 in.

[500 mm]

4 in.

[102 mm]

50° angle

39° angle

24 in.

[610 mm]

BRICK

FRONT

FLUSH
FRONT

24 in.

[610 mm]

22 3/8 in.

[568 mm]

52-7/8 in.

(1343 mm)

42 in.

[1067 mm]

Note: Grid depicts 1 inch squares.

Figure 6.3 Mantel Leg, Surround or Wall Projection (acceptable on both sides of opening)

Figure 6.4 Framing the Fireplace

C. Sidewalls/Surrounds

• Locate adjacent combustible sidewalls a minimum of 24 in. (610 mm) from fireplace opening.

• Mantle leg, surround, stub wall, whether combustible or non-combustible, may be constructed as shown in Figure 6.3.

B

C

A

2 in. (51 mm)

min. air space

clearance

from chimney.

Header MUST NOT be notched!

D

D = extra space needed for outside air connection.
If outside air duct has no bend, this dimension may be
reduced as long as minimum clearances are met.

D

A

B *

C **

D

in.

mm

305

28 3/8

74 1/2

1892

721

1368

12

Model #

* If interior of chase will be drywalled, add the thickness to this meaurement.
** Adjust header height for raised floor under fireplace.

Bir 42-B

The fireplace header cannot be positioned until

after the fireplace assembly is in place.

Framing must be extended straight up, all

the way to the ceiling.

53 7/8

Heatilator • Birmingham BIR42-B • 4059-681C • 9/12