F. Installation of Remote Condenser Unit

WARNING

1. Installation of remote condenser unit must be performed by properly trained

and certified service personnel.

2. Failure to install the equipment within these guidelines may adversely affect

safety, performance, component life, and warranty coverage.

1. Checks Before Installation

1) Remove the shipping carton, tape, and packing material.
2) Check that the refrigerant lines do not rub or touch lines or other surfaces, and that the

fan blade moves freely.

2. Location

CAUTION

1. The remote condenser unit is intended for outdoor use. Normal operating

ambient temperature should be within -20°F to +122°F (-29°C to +50°C).
Operation of the remote condenser unit, for extended periods, outside of this
normal temperature range may affect icemaker performance.

2. The maximum line length for the standard line sizes and refrigerant charge

is 66 feet. With larger line sizes and additional refrigerant, the maximum line
length is 100 feet. For details, see "II.F.5. Line Set Exceeding 66 Feet."

3. The maximum vertical distance between the remote condenser unit and the

icemaker is 33 feet above or 10 feet below the icemaker. These distances are
measured fitting to fitting. See Fig. 4.

The remote condenser unit must be positioned in a permanent site under the following
guidelines:

• A firm and flat site.
• A dry and well ventilated area with 24" (61 cm) clearance in both front and rear for

proper air circulation and ease of maintenance and/or service should they be required.
See Fig. 5.

Fig. 4

Min. 24" (61 cm) Clearance

Air

Air

Fig. 5

Icemaker

Remote

Condenser

Unit

Service Loop

Max. 33 Feet