6) Evacuate through the Schrader access ports on the Parker quick connect couplings and

charge with R-404A refrigerant vapor to a pressure of 15 to 30 PSIG.

7) Connect the refrigerant lines to the appropriate male fittings on the remote condenser

unit first and then at the icemaker. Make a proper connection as follows:

a. Remove the protective covers from the male fitting and female coupling.
b. Apply Polyol Ester (POE) refrigerant oil or Parker Super O Lube to the entire male

fitting, including O-ring, diaphragm, and threads, before making the connection. See
Fig. 8.

CAUTION

Do not use thread sealant on the fittings. Use POE refrigerant oil or Parker
Super O Lube only.

c. Make sure the male fitting and female coupling are properly aligned, then start the

connection by hand to ensure that it is not cross threaded.

d. Tighten the connection with a wrench until it is tight. At this point, the nut has

covered most of the threads on the male fitting.

e. Mark a reference line on the female coupling and the remote condenser unit or

icemaker panel. Using a backup wrench on the back of the female coupling, tighten
the six-sided nut of the female coupling an additional 1/6 turn. See Fig. 9.

8) If the line set exceeds 66 feet, see "II.F.5 Line Set Exceeding 66 Feet" for proper

charging of the unit.

Fig. 7

Female Coupling

1/2" OD Discharge Line

(Insulated)

Remote Condenser Unit

3/8" OD Liquid Line

(Insulated)

Icemaker

Male Fitting

Service Loop

Apply POE Oil or
Parker Super O Lube
to Entire Male Fitting

THREAD

SEALANT

Threads

Diaphragm

O-Ring

Fig. 8

Brush

Male Fitting

DO NOT USE

THREAD SEALANT

POLYOL

ESTER

(POE) OIL

PARKER
SUPER

O LUBE

Fig. 9

Backup

Wrench

Reference

Line

1/6

Turn

Wrench

Wrench

After Tight, Tighten an
Additional 1/6 Turn

Backup

Wrench